Basler-electric BE1-11m Manual do Utilizador

Consulte online ou descarregue Manual do Utilizador para Transmissão Basler-electric BE1-11m. Basler Electric BE1-11m User Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 0
INSTRUCTION MANUAL
FOR
BE1-11m
Motor Protection System
Publication: 9424200996
Revision: L Sep-14
Vista de página 0
1 2 3 4 5 6 ... 603 604

Resumo do Conteúdo

Página 1 - INSTRUCTION MANUAL

INSTRUCTION MANUAL FOR BE1-11m Motor Protection System Publication: 9424200996 Revision: L Sep-14

Página 2

viii 9424200996 Rev L Frequency (81) Test ...

Página 3 - Preface

88 9424200996 Rev L Protective elements blocked by 60FL should be set so that trip times are 60 milliseconds or greater to assure proper coordinati

Página 4 - Warning!

9424200996 Rev L 89 Figure 63. Power Factor Settings Screen Table 34. Operational Settings Setting Range Increment Unit of Measure Default Mode Disa

Página 5 - Contents

90 9424200996 Rev L Power Factor (55) Protection BE1-11m

Página 6

9424200996 Rev L 91 Resistance Temperature Detector (49RTD) Protection Fourteen resistance temperature detector (49RTD) elements provide over/underte

Página 7

92 9424200996 Rev L annunciate the condition and to initiate corrective action. If a target is enabled for the element, the BE1-11m will record a t

Página 8

9424200996 Rev L 93 Figure 65. Resistance Temperature Detector Settings Screen Table 36. Operational Settings Setting Range Increment Unit of Measur

Página 9

94 9424200996 Rev L Resistance Temperature Detector (49RTD) Protection BE1-11m

Página 10

9424200996 Rev L 95 Thermal Curve (49TC) Protection The thermal curve (49TC) element models the thermal capacity in a motor to provide thermal protec

Página 11

96 9424200996 Rev L restarted before the SCTC setting is exceeded the motor remains in a hot state and the timer resets at zero. t = lnIII

Página 12

9424200996 Rev L 97 Figure 66. Overload Characteristic Curves Screen Figure 67 shows the Locked Rotor Characteristic Curve screen. Figure 67. Locke

Página 13 - Introduction

9424200996 Rev L ix Breaker Control Switch (101) Test ...

Página 14 - Features

98 9424200996 Rev L The Voltage Configuration screen is shown in Figure 68. Figure 68. User Table Curve, Voltage Configuration Screen Table 37 sum

Página 15 - System Parameters

9424200996 Rev L 99 Where: TCUend = Thermal Capacity that the motor will eventually reach if current is maintained at present magnitude. τ

Página 16 - Reporting and Alarms

100 9424200996 Rev L If the pickup condition subsides before the element delay expires, the timer and Overload output are reset, no corrective acti

Página 17 - Protection and Control

9424200996 Rev L 101 Figure 70. Thermal Curve Settings Screen Table 39. Operational Settings Setting Range Increment Unit of Measure Default Mode

Página 18

102 9424200996 Rev L Thermal Curve (49TC) Protection BE1-11m

Página 19

9424200996 Rev L 103 Incomplete Sequence (48) Protection The incomplete sequence (48) element announces an incomplete sequence if the motor starts bu

Página 20 - Metering Functions

104 9424200996 Rev L Table 40. Logic Inputs and Outputs Name Function Purpose Block Input Disables the 48 function when true Trip Output True when

Página 21 - Quick Start

9424200996 Rev L 105 Starts per Time Interval (66) Protection The starts per time interval (66) element blocks the motor from starting when the user-

Página 22 - Apply Operating Power

106 9424200996 Rev L Starts per Time Interval (66) Protection BE1-11m

Página 23 - Figure 3. PWR Rear Terminals

9424200996 Rev L 107 Restart Inhibit Protection The restart inhibit function prevents motor starting when motor or system conditions dictate. A resta

Página 24

x 9424200996 Rev L Contents BE1-11m

Página 25 - Programming the BE1-11m

108 9424200996 Rev L Restart Inhibit Protection BE1-11m

Página 26 - Summary Screens

9424200996 Rev L 109 Analog Input Protection Eight analog input elements monitor external analog input signals when two remote RTD modules are connec

Página 27 - Programming Example

110 9424200996 Rev L Element Blocking The Block input provides logic-supervision control of the element. When true, the Block input disables the el

Página 28

9424200996 Rev L 111 Remote Analog Input Metering Analog input metering values are obtained through BESTCOMSPlus by using the Metering Explorer to op

Página 29

112 9424200996 Rev L Analog Input Protection BE1-11m

Página 30

9424200996 Rev L 113 Virtual Control Switches (43) Five virtual control switch (43) elements provide manual control, locally and remotely, without us

Página 31

114 9424200996 Rev L Control of Virtual Control Switches The state of the virtual control switches can be controlled through the front panel or thr

Página 32

9424200996 Rev L 115 Logic Connections Virtual control switch element logic connections are made on the BESTlogicPlus screen in BESTCOMSPlus. The vir

Página 33 - Controls and Indicators

116 9424200996 Rev L Figure 79. Virtual Control Switches Settings Screen Table 47. Operational Settings Setting Range Increment Unit of Measure De

Página 34

9424200996 Rev L 117 Logic Timers (62) Eight logic timer (62) elements emulate virtually any type of timer used in power system applications. The eig

Página 35 - Front Panel Operations

9424200996 Rev L 1 Introduction The BE1-11m Motor Protection System provides flexible, reliable, and economical protection, control, monitoring, and

Página 36 - Entering Settings

118 9424200996 Rev L Figure 81. One-Shot/Non-Retriggerable Mode One-Shot/Retriggerable Mode The one-shot retriggerable timer starts its timing seq

Página 37 - Display Setup

9424200996 Rev L 119 time delay for the output to change to false if it is presently true and the initiate input becomes false and stays false. In th

Página 38

120 9424200996 Rev L Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the Elements view, the default

Página 39 - Contact Inputs and Outputs

9424200996 Rev L 121 Table 49. Operational Settings Setting Range Increment Unit of Measure Default Mode Disabled, Pickup/Dropout, One-Shot/Non-Retri

Página 40

122 9424200996 Rev L Logic Timers (62) BE1-11m

Página 41 - Setting the Contact Inputs

9424200996 Rev L 123 Lockout Functions (86) Two lockout function (86) elements can be used to prevent operation of circuit breakers or other devices

Página 42 - Contact Outputs

124 9424200996 Rev L Table 51. Operational Settings Setting Range Increment Unit of Measure Default Mode Disabled or Enabled n/a n/a Disabled Retri

Página 43 - Relay Trouble Alarm Disable

9424200996 Rev L 125 Breaker Control Switch (101) The breaker control switch (101) element provides manual control of a circuit breaker or switch wit

Página 44 - Setting the Contact Outputs

126 9424200996 Rev L 1. Use the Metering Explorer to open the Control/Breaker Control Switch tree branch (Figure 92). 2. Click on either the TRIP

Página 45

9424200996 Rev L 127 Figure 93. Breaker Control Element Logic Block Table 52. Logic Inputs and Outputs Name Logic Function Purpose Trip Input Sets t

Página 46

2 9424200996 Rev L Features The BE1-11m protection system includes many features for the protection, monitoring, and control of power system equipm

Página 47

128 9424200996 Rev L Breaker Control Switch (101) BE1-11m

Página 48

9424200996 Rev L 129 Setting Groups Four setting groups allow for adapting the coordination settings to optimize them for a predictable situation. Se

Página 49

130 9424200996 Rev L Discrete Inputs When the setting group selection function block is enabled for Discrete Inputs, there is a direct correlation

Página 50

9424200996 Rev L 131 Figure 96. Input Control Binary Inputs CT Source The CT Source setting configures the setting group selection function to monit

Página 51 - Protection

132 9424200996 Rev L to an alternate setting group that can accommodate the condition. The BE1-11m can be set to alarm for this condition using the

Página 52

9424200996 Rev L 133 Figure 97. Setting Group Logic Block Table 55. Logic Inputs and Outputs Name Logic Function Purpose Automatic Input True when

Página 53

134 9424200996 Rev L Figure 98. Setting Group Setup Screen Table 56. Operational Settings Setting Range Purpose Default Mode Disabled Discrete Inp

Página 54

9424200996 Rev L 135 Setting Range Purpose Default Monitor Setting Disable, IP, IG, I2, 3I0, 60FL Determines when automatic setting group changes occ

Página 55

136 9424200996 Rev L Setting Groups BE1-11m

Página 56

9424200996 Rev L 137 Metering The BE1-11m measures the voltage and current inputs, displays those values in real time, records those values every qua

Página 57

9424200996 Rev L 3 capacitor nears depletion, the backup battery takes over and maintains timekeeping. The backup battery has a life expectancy of gr

Página 58 - Pickup and Trip

138 9424200996 Rev L Table 57. Explanation of Figure 100 Call-Outs Call-Out Explanation A Holding the left mouse button down on a metering tab and

Página 59

9424200996 Rev L 139 Figure 101. Analog Metering, Voltage Screen Current - Primary and Secondary Metered current includes primary and secondary phas

Página 60

140 9424200996 Rev L Reactive Power Reactive power is metered over a range of −7,500 kilovars to +7,500 kilovars on five ampere nominal systems. On

Página 61 - Frequency (81) Protection

9424200996 Rev L 141 Figure 104. Analog Metering, Frequency Screen Differential The differential value is calculated as shown in the following equat

Página 62 - Voltage Inhibit

142 9424200996 Rev L Figure 105. Analog Metering, Differential Screen Energy Energy is metered for positive and negative watthours and varhours. W

Página 63

9424200996 Rev L 143 Click the Edit button to change the values. The Meter Energy Editor screen appears as shown in Figure 107. Make the desired chan

Página 64

144 9424200996 Rev L Figure 110. RTD Meter Screen Motor Metering Use the Metering Explorer in BESTCOMSPlus to open the following Motor Meter scree

Página 65

9424200996 Rev L 145 Sequence of Events A sequence of events recorder (SER) report is very useful in reconstructing the exact sequence and timing of

Página 66

146 9424200996 Rev L Figure 112. Sequence of Events Screen Viewing SER Data through the Web Page Interface Sequence of events summary can be viewe

Página 67

9424200996 Rev L 147 Fault Reporting The fault reporting function records and reports information about faults that have been detected by the BE1-11m

Página 68

4 9424200996 Rev L each output and to each state (energized and de-energized) for use in reporting functions. Output logic can be overridden to ope

Página 69

148 9424200996 Rev L Table 60. Targets as Displayed Target Description 27P-#-A/B/C Phase Undervoltage, A, B, or C 32-#-A/B/C/T-Over Power, Phase A,

Página 70 - Coordination Settings

9424200996 Rev L 149 Target Settings Targets are enabled using BESTCOMSPlus. Use the Settings Explorer to open the Target Configuration tree branch.

Página 71

150 9424200996 Rev L Figure 116. Target Reset Logic Block Pressing the front-panel Reset key clears the targets and the Trip LED. Depending on dev

Página 72

9424200996 Rev L 151 Figure 117. Fault Reports Screen Viewing and Downloading Fault Data through the Web Page Interface Fault report data can be vie

Página 73

152 9424200996 Rev L • Station ID, Device ID, and User ID. These lines report station, device, and user information as defined by BESTCOMSPlus on

Página 74

9424200996 Rev L 153 power system cycle two cycles prior to the end of the fault. Refer to Figure 119 and Table 62, call-out F. • IG, IG Circuit 2.

Página 75

154 9424200996 Rev L Figure 118. Fault Records Screen Table 61 summarizes the oscillographic records settings. Table 61. Oscillographic Records Se

Página 76

9424200996 Rev L 155 Protective Fault Analysis Figure 119. Protective Fault Analysis Protective element picks upProtective element tripsBreaker aux

Página 77

156 9424200996 Rev L Table 62. Legend for Figure 119 Locator Description A A fault summary report and an oscillograph record are triggered when the

Página 78

9424200996 Rev L 157 Motor Reporting The motor reporting function records and reports information about motor operation. The BE1-11m provides many re

Página 79

9424200996 Rev L 5 Fault Reporting Fault reports consist of simple target information, fault summary reports, and detailed oscillography records to e

Página 80

158 9424200996 Rev L  =  × 100% Equation 19. Voltage Unbalance Start Records The BE1-11m records information

Página 81

9424200996 Rev L 159 • Min Voltage - This line reports the minimum of the phase voltages during the motor start. • Max Thermal Capacity - This line

Página 82

160 9424200996 Rev L Figure 125. Total Starts Screen The Start Data screen is shown in Figure 126. Click the Edit button to reset or change the va

Página 83 - × 51   

9424200996 Rev L 161 Figure 128. Learned Motor Data Screen BE1-11m Motor Reporting

Página 84

162 9424200996 Rev L Motor Reporting BE1-11m

Página 85

9424200996 Rev L 163 Alarms The BE1-11m monitors internal systems, external interfaces, and power system equipment and annunciates an alarm when one

Página 86

164 9424200996 Rev L Name Description I2 Demand Negative-sequence current unbalance demand IG Demand Ground current demand IP Demand Phase current

Página 87

9424200996 Rev L 165 Name Description Setting Change Setting change made by user Settings Group 0 Setting group 0 is active Settings Group 1 Setting

Página 88

166 9424200996 Rev L under Alarm Configuration. When active, the label of a user alarm is displayed on the Alarms screen on the front-panel display

Página 89

9424200996 Rev L 167 Reset will reset all logic alarms. Use the drag-and-drop method to connect a variable or series of variables to the Reset input.

Página 90

6 9424200996 Rev L Breaker Failure (50BF) Protection One breaker failure function provides protection and security for the power system against fai

Página 91 - Power (32) Protection

168 9424200996 Rev L Alarms BE1-11m

Página 92 - Direction of Power Flow

9424200996 Rev L 169 Breaker Monitoring Breaker monitoring helps manage equipment inspection and maintenance expenses by providing extensive monitori

Página 93

170 9424200996 Rev L edit this value at the front-panel display. To view the breaker status using BESTCOMSPlus, use the Metering Explorer to open t

Página 94

9424200996 Rev L 171 Figure 135. Protective Fault Analysis Protective element picks upProtective element tripsBreaker auxiliary contact changes sta

Página 95 - (40Q) Protection

172 9424200996 Rev L Table 65. Legend for Figure 135 Locator Description A A fault summary report and an oscillograph record are triggered when the

Página 96

9424200996 Rev L 173 Figure 136. Breaker Monitoring Screen To connect the Block logic input, use the Settings Explorer within BESTCOMSPlus to open t

Página 97

174 9424200996 Rev L be read or changed through the communication ports using BESTCOMSPlus. Use the Metering Explorer to open the Reports, Breaker

Página 98

9424200996 Rev L 175 Demands Demand recording promotes the ability of an electric power provider to plan for future upgrades. For example, increasing

Página 99 - Power Factor (55) Protection

176 9424200996 Rev L Setting Range Increment Unit of Measure Default Phase Current Threshold 0 or 0.5 to 16 0.01 amps 0 Neutral/Ground Current Th

Página 100 - Operational Settings

9424200996 Rev L 177 Figure 140. Demand Current Screen Figure 141. Demand Power Screen Refer to the BESTnet™Plus chapter for information on viewing

Página 101

9424200996 Rev L 7 Resistance Temperature Detector (49RTD) Fourteen resistance temperature detector elements provide over/undertemperature protection

Página 102

178 9424200996 Rev L Demands BE1-11m

Página 103 - (49RTD) Protection

9424200996 Rev L 179 Load Profile The load profile recording function provides a running average of the demand and helps a customer determine when po

Página 104

180 9424200996 Rev L Load Profile BE1-11m

Página 105 - Remote RTD Metering

9424200996 Rev L 181 Power Quality The BE1-11m offers class B power quality measurement performance as defined by IEC 610004-30. Power quality data c

Página 106

182 9424200996 Rev L Voltage Figure 144 illustrates the Power Quality, Voltage screen. Figure 144. Power Quality, Voltage Screen 10-Second Frequen

Página 107 - Element Operation

9424200996 Rev L 183 Figure 146. Power Quality, Dip/Swell Screen Harmonics Figure 147 illustrates the Power Quality, Harmonic Voltage screen. The Ha

Página 108 - Equation 6. Cold Curve

184 9424200996 Rev L Power Quality BE1-11m

Página 109

9424200996 Rev L 185 Trip Circuit Monitor (52TCM) A trip circuit monitor (52TCM) element continually monitors the circuit breaker trip circuit for vo

Página 110 - Equation 8. TCU

186 9424200996 Rev L Figure 148. Trip Detector Circuit Table 72. Current Draw for each Power Supply Voltage Rating Power Supply Voltage Rating Re

Página 111 - Equation 10. RTD Bias TCU

9424200996 Rev L 187 Figure 149 illustrates typical trip circuit monitor connections for the BE1-11m. Figure 149. Trip Circuit Voltage and Continuit

Página 113

8 9424200996 Rev L Refer to the BESTlogicPlus chapter for more information on logic schemes. Custom logic settings allow you to tailor the BE1-11m

Página 114

188 9424200996 Rev L Figure 150. TCM with Other Devices Trip Circuit Monitor (52TCM) Enable/Disable Jumper Note A BE1-11m in a J type case is del

Página 115

9424200996 Rev L 189 Figure 151. Trip Circuit Monitor Enable/Disable Jumper Location Logic Connections Trip circuit monitor logic connections are ma

Página 116

190 9424200996 Rev L Operational Settings Trip circuit monitor element operational settings are configured on the Trip Circuit Monitor (52TCM) sett

Página 117

9424200996 Rev L 191 Fuse Loss (60FL) The fuse loss (60FL) element detects fuse loss or loss of potential in a three-phase system. Element logic conn

Página 118

192 9424200996 Rev L Table 75. Fuse Loss Logic Parameters Input True Condition A Positive-sequence volts greater than 8.8% of the nominal voltage;

Página 119 - Restart Inhibit Protection

9424200996 Rev L 193 Table 76. Logic Output Name Logic Function Purpose Fuse Loss Output True when the 60FL logic is true Operational Settings Fuse l

Página 120

194 9424200996 Rev L Fuse Loss (60FL) BE1-11m

Página 121 - Analog Input Protection

9424200996 Rev L 195 BESTnet™Plus BE1-11m Motor Protection Systems with an Ethernet port have a web page interface that can be used to view BE1-11m s

Página 122

196 9424200996 Rev L Figure 159. Real Time Data Page Demand Data Figure 160 illustrates the Demand Data page. Present and peak demand values are s

Página 123 - Remote Analog Input Metering

9424200996 Rev L 197 Figure 160. Demand Data Page Faults Fault Summary Figure 161 illustrates the Fault Summary page. To view fault details and down

Página 124

9424200996 Rev L 9 Quick Start This chapter provides basic installation and setup information about the BE1-11m Motor Protection System. BE1-11m prot

Página 125

198 9424200996 Rev L Figure 161. Fault Summary Page Fault Details Figure 162 illustrates the Fault Details page. Use the buttons to download oscil

Página 126

9424200996 Rev L 199 Sequence of Events Figure 163 illustrates the Sequence of Events Summary page. A summary of the sequence of events is shown on t

Página 127

200 9424200996 Rev L Figure 164. Power Quality Page BESTnet™Plus BE1-11m

Página 128

9424200996 Rev L 201 Mounting BE1-11m protection systems are supplied in a non-drawout, S1 size case (J option) that fits in a standard S1 case openi

Página 129 - Logic Timers (62)

202 9424200996 Rev L Figure 166. Case Side Dimensions 7.91 [201.03]6.26 [159.08]1.03 [26.15]0.62 [15.62]0.41 [10.31]0.30 [7.68]8.41 [213.65]Mou

Página 130 - Initiate

9424200996 Rev L 203 Case cutout and drilling dimensions are shown in Figure 167. Figure 167. Case Cutout and Drilling Dimensions 3.03 (77.0)6.06

Página 131 - Element Blocking

204 9424200996 Rev L An adapter plate to mount a J case in a GE S2 or ABB FT-21 cutout is shown in Figure 168. Order Basler part number 9108551021.

Página 132

9424200996 Rev L 205 An adapter plate to mount a J case in a ABB FT-32/FT-32 cutout is shown in Figure 169. Order Basler part number 9108551022. Fig

Página 133

206 9424200996 Rev L An adapter plate to mount a J case in a GE M1/M2 cutout or Basler M1 cutout is shown in Figure 170. Order Basler part number 9

Página 134

9424200996 Rev L 207 A J case retrofit mounting plate for the Multilin 469 consists of two parts. See Figure 171 and Figure 172. Order Basler part nu

Página 135 - Lockout Functions (86)

10 9424200996 Rev L Table 1. System Recommendations for BESTCOMSPlus and the .NET Framework System Type Component Recommendation 32/64 bit Processo

Página 136

208 9424200996 Rev L Figure 172. Retrofit Mounting Plate (Basler P/N: 9424200073) – Part 2 Mounting BE1-11m

Página 137 - Breaker Control Switch (101)

9424200996 Rev L 209 A J case retrofit mounting plate for a non-drawout Multilin 269/369 is shown in Figure 173. Order Basler part number 9424200074.

Página 138

210 9424200996 Rev L A J case retrofit mounting plate for a drawout Multilin 269 is shown in Figure 174. Order Basler part number 9424200075. Figu

Página 139

9424200996 Rev L 211 A pivoting projection-mounting kit for a J case is shown in Figure X. When installed, this kit provides rear access to connectio

Página 140

212 9424200996 Rev L Mounting BE1-11m

Página 141 - Setting Groups

9424200996 Rev L 213 Terminals and Connectors Connections to the BE1-11m are dependent on the application and logic scheme selected by the user. As a

Página 142 - 05-03-06

214 9424200996 Rev L Figure 177. Rear-Panel Connections with Fiber Optic Ethernet Terminal Blocks J-style cases use two sizes of terminal blocks.

Página 143 - Alarm and Timer

9424200996 Rev L 215 On occasion, however, protection engineers will encounter situations where CT polarity is reversed for a specific application. T

Página 144

216 9424200996 Rev L Figure 180. Example of Reversed CT Polarity Terminals and Connectors BE1-11m

Página 145

9424200996 Rev L 217 Typical Connections Typical external dc connections for the BE1-11m are shown in Figure 181. Figure 181. Typical External DC C

Página 146

9424200996 Rev L 11 Figure 2. Front Panel Label Example Connect rear terminals A6, A7, and A8 (ground) to a power supply. See Figure 3. Apply operat

Página 147

218 9424200996 Rev L Typical external ac connections for three-phase are shown in Figure 182. Figure 182. Typical AC Connections for Three-Phase C

Página 148

9424200996 Rev L 219 Three-phase voltage sensing, alternate VT inputs are shown in Figure 183. Figure 183. Three-Phase Voltage Sensing, Alternate VT

Página 149 - Metering

220 9424200996 Rev L Single-phase current sensing connections are shown in Figure 184. Figure 184. Single-Phase Current Sensing Connections Note

Página 150 - Analog Metering Functions

9424200996 Rev L 221 BESTCOMSPlus® Software BESTCOMSPlus is a Windows®-based, PC application that provides a user-friendly, graphical user interface

Página 151

222 9424200996 Rev L Installation BESTCOMSPlus software is built on the Microsoft® .NET Framework. The setup utility that installs BESTCOMSPlus on

Página 152 - Frequency

9424200996 Rev L 223 Connect a USB Cable The USB driver was copied to your PC during BESTCOMSPlus installation and is installed automatically after p

Página 153

224 9424200996 Rev L Figure 188. Communication Pull-Down Menu Figure 189. BE1-11 Connection Screen Manual Activation of the BE1-11 Plugin Manual

Página 154 - × Secondary Watts or Vars

9424200996 Rev L 225 Figure 190. Device Plugin Requires Activation The Activate Device Plugin pop-up appears. Refer to Figure 191. Figure 191. Acti

Página 155 - RTD Meter

226 9424200996 Rev L Figure 192. Activation Key Email Figure 193. Activate Device Plugin Establishing Communication Communication between BESTCOM

Página 156 - Motor Metering

9424200996 Rev L 227 Advanced Properties Click the Advanced button on the Connection screen to display the Advanced Properties dialog. Default settin

Página 157 - Sequence of Events

12 9424200996 Rev L Figure 4. BESTCOMSPlus Select Language Screen The BESTCOMSPlus splash screen is shown for a brief time. See Figure 5. Figure

Página 158

228 9424200996 Rev L Menu Item Description Communication New Connection Choose new device or BE1-11 Close Connection Close communication between BE

Página 159 - Fault Reporting

9424200996 Rev L 229 Table 80. Lower Menu Bar (BE1-11 Plugin) Menu Button Description Enables you to show/hide the Metering Panel, Settings Panel, o

Página 160

230 9424200996 Rev L Metering Explorer The Metering Explorer is described in the Metering chapter. Settings File Management A settings file contain

Página 161 - Target Settings

9424200996 Rev L 231 Figure 196. Processing, Please Wait… Printing a Settings File To view a preview of the settings printout, select Print Preview

Página 162 - Fault Reports

232 9424200996 Rev L Figure 198. BESTCOMSPlus Settings Compare Auto Export Metering The auto export metering function automatically exports meteri

Página 163 - Fault Summary Report Items

9424200996 Rev L 233 BESTCOMSPlus Updates Ongoing BE1-11m functionality enhancements may make future BE1-11m firmware updates desirable. Enhancements

Página 164

234 9424200996 Rev L BESTCOMSPlus® Software BE1-11m

Página 165 - Oscillographic Records

9424200996 Rev L 235 BESTlogic™Plus BESTlogicPlus Programmable Logic is a programming method used for managing the input, output, protection, control

Página 166

236 9424200996 Rev L BESTlogic™Plus Composition There are three main groups of objects used for programming BESTlogicPlus. These groups are I/O, Co

Página 167 - Protective Fault Analysis

9424200996 Rev L 237 Name Description Symbol Major Alarm True when the Major Alarm is true. Refer to the Alarms chapter for more information. Minor

Página 168

9424200996 Rev L 13 Figure 6. Communication Pull-Down Menu Figure 7. BE1-11 Connection Screen Programming the BE1-11m This section contains an intr

Página 169 - Motor Reporting

238 9424200996 Rev L Name Description Symbol Pickup and Dropout Timers Pickup Up Timer A pickup timer produces a true output when the elapsed time

Página 170 -  

9424200996 Rev L 239 Elements This group contains elements for the 27P, 32, 37, 40Q, 43, 48, 49RTD, 49TC, 50, 50BF, 51, 55, 59P, 59X, 60FL, 62, 81, 8

Página 171 - Motor Maintenance Data

240 9424200996 Rev L Name Description Symbol 49TC Thermal Curve Protection. Refer to the Thermal Curve (49TC) Protection chapter. 50-x Instantaneo

Página 172 - Learned Motor Data

9424200996 Rev L 241 Name Description Symbol 81-x Frequency Protection. Refer to the Frequency (81) Protection chapter. 87 Current Differential Prot

Página 173 - BE1-11m Motor Reporting

242 9424200996 Rev L Name Description Symbol 101 Breaker Control Switch. Refer to the Breaker Control Switch (101) chapter. BESTlogic™Plus BE1-

Página 174

9424200996 Rev L 243 Name Description Symbol MOTORSTATUS Motor Status. ● Logic Inputs ○ Block – This input drives the Start Blocked output true and

Página 175 - Table 63. Available Alarms

244 9424200996 Rev L Name Description Symbol Reporting and Alarms 52TCM Trip Circuit Monitor. Refer to the Trip Circuit Monitor (52TCM) chapter. 6

Página 176

9424200996 Rev L 245 Name Description Symbol TARGETRESET Target Reset. Refer to the Fault Reporting chapter. USERALARMx User Alarms 1 through 16. Re

Página 177 - User Programmable Alarms

246 9424200996 Rev L Caution Always remove the BE1-11m from service prior to changing or modifying the active logic scheme. Attempting to modify a

Página 178 - Resetting Alarms

9424200996 Rev L 247 Logic Page 1 Figure 201 illustrates the default logic on Logic Page 1 in BESTlogicPlus. Figure 201. Logic Page 1 for Default Lo

Página 179

14 9424200996 Rev L BESTlogic™Plus Programmable Logic is used to program BE1-11m logic for protection elements, inputs, outputs, alarms, etc. This

Página 180

248 9424200996 Rev L Logic Page 2 Figure 202 illustrates the default logic on Logic Page 2 in BESTlogicPlus. Figure 202. Logic Page 2 for Default

Página 181 - Breaker Monitoring

9424200996 Rev L 249 Logic Page 3 Figure 203 illustrates the default logic on Logic Page 3 in BESTlogicPlus. Figure 203. Logic Page 3 for Default Lo

Página 182 - Breaker Duty Monitoring

250 9424200996 Rev L Logic Page 4 Figure 204 illustrates the default logic on Logic Page 4 in BESTlogicPlus. Figure 204. Logic Page 4 for Default

Página 183 - 03-23-06

9424200996 Rev L 251 Logic Page 5 Figure 205 illustrates the default logic on Logic Page 5 in BESTlogicPlus. Figure 205. Logic Page 5 for Default Lo

Página 184

252 9424200996 Rev L BE1-11m by selecting Upload Settings and Logic to Device or Upload Logic to Device on the Communication pull-down menu. Progra

Página 185

9424200996 Rev L 253 Next, open the Components tab inside the BESTlogicPlus window and drag a timer onto the program grid. Right click on the timer t

Página 186 - Breaker Alarms

254 9424200996 Rev L BESTlogic™Plus File Management To manage BESTlogicPlus files, use the Settings Explorer to open the BESTlogicPlus Programmable

Página 187 - Demands

9424200996 Rev L 255 You can skip the print preview and go directly to print by clicking on the Printer icon on the BESTlogicPlus Programmable Logic

Página 188

256 9424200996 Rev L BESTlogic™Plus BE1-11m

Página 189

9424200996 Rev L 257 Communication This chapter describes the connections and settings for BE1-11m communication. In addition to standard USB, RS-485

Página 190

9424200996 Rev L 15 color is gray. The System Summary screen is available by clicking BE1-11 in the Settings Explorer as shown in Figure 10. Summary

Página 191 - Load Profile

258 9424200996 Rev L Figure 211. RS-485 DB-37 to BE1-11m Ethernet Setup Located on the rear panel, the optional Ethernet communication port provid

Página 192

9424200996 Rev L 259 5. Select Configure, Ethernet from the Communication pull-down menu. If the BE1-11m is connected properly, the Configure Ethern

Página 193 - Power Quality

260 9424200996 Rev L Note The PC running BESTCOMSPlus software must be configured correctly to communicate with the BE1-11m. The PC must have an IP

Página 194 - Dip/Swell

9424200996 Rev L 261 215. Use the drag-and-drop method to connect a variable or series of variables to the input. Refer to the BESTlogicPlus chapter

Página 195 - Harmonics

262 9424200996 Rev L Figure 217. DNP Settings, Miscellaneous Settings Screen Unsolicited Response Support The Unsolicited Response Support screen

Página 196

9424200996 Rev L 263 Figure 219. Default Variations Screen DNP Analog Points Mapping Analog points can be mapped to any of the available analog user

Página 197 - Trip Circuit Monitor (52TCM)

264 9424200996 Rev L DNP Binary Points Mapping Binary points can be mapped to any of the available binary user map registers. Use the Settings Expl

Página 198

9424200996 Rev L 265 Modbus™ Setup Settings for Modbus are made by using the Settings Explorer to open the Communications, Modbus tree branch. Settin

Página 199 - Caution

266 9424200996 Rev L Figure 224. Modbus Mapping Screen Communication BE1-11m

Página 200

9424200996 Rev L 267 Security Multiple levels of BE1-11m security give personnel the level of access appropriate for the tasks they routinely perform

Página 201

16 9424200996 Rev L Figure 11. Motor Configuration Screen Step 7: In the Settings Explorer, expand Protection, Current and select the Instantaneo

Página 202

268 9424200996 Rev L 2. Enter the username and password of the administrator and then click the Log In button. The default Administrator username

Página 203 - Fuse Loss (60FL)

9424200996 Rev L 269 2. The Login dialog box pops up. See Figure 225. An administrator access level is required to set up port access. Enter the use

Página 204

270 9424200996 Rev L Table 89. Settings for Access Control Setting Range Increment Unit Default Access Timeout Delay 10 to 3,600 1 seconds 300 Logi

Página 205

9424200996 Rev L 271 Timekeeping The BE1-11m provides a real-time clock with capacitor backup that is capable of operating the clock for up to 24 hou

Página 206

272 9424200996 Rev L Figure 230. Clock Setup Screen Table 90. Settings for Clock Setting Range Increment Unit Default Time Zone Hour Offset –12 to

Página 207 - BESTnet™Plus

9424200996 Rev L 273 Figure 231. Status, Real Time Clock Screen IRIG Port IRIG time code signal connections are located on the rear panel. When a va

Página 208 - Demand Data

274 9424200996 Rev L Backup Battery for the Real-Time Clock The backup battery for the real time clock is a standard feature of the BE1-11m. A batt

Página 209 - Fault Summary

9424200996 Rev L 275 Figure 232. Front-Panel Circuit Board, Backup Battery Location BE1-11m Timekeeping

Página 210 - Fault Details

276 9424200996 Rev L Figure 233. Re-Attaching the Front Cover Timekeeping BE1-11m

Página 211

9424200996 Rev L 277 Device Information BE1-11m identification labels, firmware version, serial number, and style number are found on the Device Info

Página 212 - BESTnet™Plus BE1-11m

9424200996 Rev L 17 Figure 12. Instantaneous Overcurrent (50-4) Screen Figure 13. BESTlogicPlus Logic Page 3 Step 10: In this step, the Pickup outp

Página 213 - Mounting

278 9424200996 Rev L Device Info Information about a BE1-11m communicating with BESTCOMSPlus can be obtained on the Device Info screen of BESTCOMSP

Página 214 - Mounting BE1-11m

9424200996 Rev L 279 screen in BESTCOMSPlus. The Basler Electric Device Package Uploader screen will appear. See Figure 236. Figure 236. Basler Elec

Página 215 - BE1-11m Mounting

280 9424200996 Rev L Device Information BE1-11m

Página 216

9424200996 Rev L 281 Configuration BE1-11m inputs consist of three-phase current inputs and ground, three-phase voltage inputs, and one auxiliary vol

Página 217

282 9424200996 Rev L VT Connections When four-wire VT connections are used, the BE1-11m measures the three-phase to neutral voltages and calculates

Página 218

9424200996 Rev L 283 For Sensing Type: Four-wire )cos(IVWattsAAANAφ= )cos(IVWattsBBBNBφ= )cos(IVWattsCCCNCφ= CBA3WWWWatts ++=φ )sin(IVVarsAAANAφ=

Página 219

284 9424200996 Rev L BC Sensing: °−∠⋅= 901VVABAN31 °∠⋅= 301VVABBN31 °∠⋅= 1501VVABCN31 CA Sensing: °∠⋅= 1501VVABAN31 °−∠⋅=901VVABBN31 °∠⋅= 301VVABCN

Página 220 - 208 9424200996 Rev L

9424200996 Rev L 285 Start/Stop Contacts The Motor Status logic element provides the operating status of the motor. It identifies the motor as starti

Página 221

286 9424200996 Rev L Setting Range Increment Unit Default Nominal Aux Voltage 50 to 300 0.01 volts 69.3 Power Polarity Normal or Reverse n/a n/a

Página 222

9424200996 Rev L 287 Tap This setting adjusts the measured currents to eliminate magnitude mismatch prior to being used by the optional 87 differenti

Página 223

9424200996 Rev L i Preface This instruction manual provides information about the installation and operation of the BE1-11m Motor Protection System.

Página 224

18 9424200996 Rev L Figure 14. BESTlogicPlus Logic Page 4 Figure 15. BESTlogicPlus Programming OUT4 Step 11: In this step, the Pickup output of t

Página 225 - Terminals and Connectors

288 9424200996 Rev L Setting Range Increment Unit Default CT Source* CT1 or CT2 n/a n/a CT1 Phase VT Ratio 1 to 10,000 0.01 turns ratio 1 Phase V

Página 226 - CT Polarity

9424200996 Rev L 289 Introduction to Testing The need to test protection systems to confirm performance as designed by manufacturers has always exist

Página 227

290 9424200996 Rev L • Setting validation • Proper operation of equipment (main or auxiliary) • Proper alarming (to SCADA) and/or targeting Peri

Página 228

9424200996 Rev L 291 BE1-11m Self-Test All internal circuitry and software that affect the BE1-11m core functionality are monitored by the continuous

Página 229 - BE1-11m Typical Connections

292 9424200996 Rev L Introduction to Testing BE1-11m

Página 230

9424200996 Rev L 293 Acceptance Testing Although Basler Electric performs detailed acceptance testing on all new protection systems, it is generally

Página 231 - 9424200996 Rev L 219

294 9424200996 Rev L IRIG Verification (if used) Purpose: To verify that the BE1-11m acquires and updates IRIG time and date information. Step 1:

Página 232

9424200996 Rev L 295 Step 7: Use the Metering Explorer in BESTCOMSPlus to return to the Control, Output Override screen and click on the Enabled b

Página 233 - BESTCOMSPlus® Software

296 9424200996 Rev L current measurements can also be verified on the Metering > Analog Metering > Current > Current Circuit 2 > Second

Página 234 - Installation

9424200996 Rev L 297 Applied Voltage Measured Voltage Lower Limit Upper Limit 120 volts 119.4 V 120.6 V 140 volts 139.3 V 140.7 V 160 volts 159.2 V 1

Página 235 - Connect a USB Cable

9424200996 Rev L 19 Figure 16. BESTlogicPlus Programming User Alarm 1 Figure 17. BESTlogicPlus Toolbar Step 13: In the Settings Explorer, expand Pr

Página 236

298 9424200996 Rev L Step 3: Connect BE1-11m Terminals C17 (polarity) and C18 to a 180 Hz (third harmonic) ac voltage source. Step 4: Apply t

Página 237

9424200996 Rev L 299 Commissioning Testing Special precautions should be taken to ensure that all tests are performed with safety as the greatest con

Página 238 - Establishing Communication

300 9424200996 Rev L original state. Use the Metering Explorer in BESTCOMSPlus to open the Reports, Sequence of Events screen. Click on the Downloa

Página 239 - Menu Bars

9424200996 Rev L 301 Protection and Control Function Verification Before placing the BE1-11m in service, the user should ensure that all system ac an

Página 240

302 9424200996 Rev L Energy Data and Demand BESTCOMSPlus Navigation Path: Metering Explorer, Demand HMI Navigation Path: Metering Explorer, Demand

Página 241 - Settings Explorer

9424200996 Rev L 303 Fault Summary Reports BESTCOMSPlus Navigation Path: Metering Explorer, Reports, Fault Records HMI Navigation Path: Metering Expl

Página 242 - Settings File Management

304 9424200996 Rev L Commissioning Testing BE1-11m

Página 243 - Comparing Settings Files

9424200996 Rev L 305 Periodic Testing Because the BE1-11m has extensive internal test capabilities, periodic testing of the protection system can be

Página 244 - Auto Export Metering

306 9424200996 Rev L Note If verifying the analog measurement circuits by comparison to independent devices is used, you should ensure that the two

Página 245 - Firmware Updates

9424200996 Rev L 307 Phase Undervoltage (27P) Test Functional testing is a way to assess this protection system’s suitability for your application. F

Página 246

20 9424200996 Rev L Figure 19. User Programmable Alarms Screen Step 15: Figure 20 shows the user-defined labels of OUT4 and USERALM1 that were nam

Página 247 - BESTlogic™Plus

308 9424200996 Rev L Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 241. • Blocking is disabled. •

Página 248 - BESTlogic™Plus Composition

9424200996 Rev L 309 Step 2: Prepare to monitor the 27P-1 timings. Timing accuracy is verified by measuring the elapsed time between a sensing volta

Página 249

310 9424200996 Rev L Phase Undervoltage (27P) Test BE1-11m

Página 250 - BESTlogic™Plus BE1-11m

9424200996 Rev L 311 Phase Overvoltage (59P) Test Functional testing is a way to assess this protection system’s suitability for your application. Fu

Página 251

312 9424200996 Rev L Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 242. • Blocking is disabled. •

Página 252 - 240 9424200996 Rev L

9424200996 Rev L 313 Step 2: Prepare to monitor the 59P-1 timings. Timing accuracy is verified by measuring the elapsed time between a sensing volta

Página 253 - BE1-11m BESTlogic™Plus

314 9424200996 Rev L Phase Overvoltage (59P) Test BE1-11m

Página 254 - 242 9424200996 Rev L

9424200996 Rev L 315 Auxiliary Overvoltage (59X) Test Functional testing is a way to assess this protection system’s suitability for your application

Página 255 - 9424200996 Rev L 243

316 9424200996 Rev L Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 243. • Blocking is disabled. •

Página 256 - 244 9424200996 Rev L

9424200996 Rev L 317 Step 2: Prepare to monitor the 59X-1 timings. Timing accuracy is verified by measuring the elapsed time between a sensing volta

Página 257 - Logic Schemes

9424200996 Rev L 21 Controls and Indicators BE1-11m controls and indicators are located on the front panel and include sealed membrane switches, LED

Página 258

318 9424200996 Rev L Table 110. Pickup Test Settings (V1 Mode) Pickup Setting Time Delay 82 V 50 ms 42 V 50 ms 25 V 50 ms Step 4: Prepare to monit

Página 259

9424200996 Rev L 319 Table 112. Operational Settings (V2 Mode) Setting Value BESTCOMSPlus Screen Description Phase VT Ratio 1 System Parameters, Sens

Página 260

320 9424200996 Rev L Step 7: Verify the pickup and dropout accuracy at 120 Vac for a pickup setting of 42 V (126 Vac on test set) and 70 Vac for a

Página 261

9424200996 Rev L 321 Figure 246. BESTlogicPlus Settings (Vx Fundamental Mode) Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Overvolta

Página 262

322 9424200996 Rev L Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 117. Record the results. Step 6: (Optional

Página 263

9424200996 Rev L 323 Step 5: Connect and apply a single-phase, 120 Vac, 3rd harmonic voltage source to the Vx input, terminals C17 (polarity) and C1

Página 264 - Programming BESTlogic™Plus

324 9424200996 Rev L Timing Verification (3V0 Mode) Time Delay Range = 50 to 600,000 ms Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater

Página 265 - Offline Logic Simulator

9424200996 Rev L 325 Step Time Delay Setting Low Actual Timing High Pass/Fail 4 2,000 ms 1,968 ms 2,032 ms P / F 5 5,000 ms 4,968 ms 5,032 ms P

Página 266

326 9424200996 Rev L Auxiliary Overvoltage (59X) Test BE1-11m

Página 267 - BESTlogic™Plus Examples

9424200996 Rev L 327 Frequency (81) Test Functional testing is a way to assess this protection system’s suitability for your application. Functional

Página 268

22 9424200996 Rev L Table 2. Front Panel Descriptions Locator Description A Power Indicator – This green LED lights when operating power is applied

Página 269 - Communication

328 9424200996 Rev L Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 248. • Blocking is disabled. •

Página 270 - Ethernet Setup

9424200996 Rev L 329 Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 249. • Blocking is disabled. • O

Página 271

330 9424200996 Rev L Step 3: Connect and apply a 120 Vac, 60-hertz voltage source to terminals C13 (A-phase) and C16 (neutral). Step 4: Step

Página 272 - Email Setup

9424200996 Rev L 331 Step 4: Connect a 120 Vac voltage source capable of smoothly sweeping the frequency from 35 Hz to 75 Hz to terminals C13 (A-p

Página 273 - DNP Setup

332 9424200996 Rev L Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 251. • Blocking is disabled. •

Página 274

9424200996 Rev L 333 Underfrequency Pickup Verification Pickup Setting Range = 15 to 70 Hz Pickup Accuracy = ±0.01 Hz Reset = 0.02 Hz ±0.01 Hz of the

Página 275 - DNP Analog Points Mapping

334 9424200996 Rev L Frequency (81) Test BE1-11m

Página 276 - DNP Binary Points Mapping

9424200996 Rev L 335 Instantaneous Undercurrent (37) Test Functional testing is a way to assess this protection system’s suitability for your applica

Página 277 - Modbus™ Setup

336 9424200996 Rev L Figure 252. BESTlogicPlus Settings Step 3: Use BESTCOMSPlus to open the Protection, Current, Instantaneous Undercurrent (3

Página 278 - Communication BE1-11m

9424200996 Rev L 337 Step 2: Prepare to monitor the 37 timings. Timing accuracy is verified by measuring the elapsed time between a sensing current

Página 279 - Security

9424200996 Rev L 23 Locator Description Q Identification Label – This label lists the style number, serial number, sensing input current and voltage

Página 280 - Port Access Setup

338 9424200996 Rev L Instantaneous Undercurrent (37) Test BE1-11m

Página 281 - Access Control

9424200996 Rev L 339 Instantaneous Overcurrent (50) Test Functional testing is a way to assess this protection system’s suitability for your applicat

Página 282 - Viewing the Security Log

340 9424200996 Rev L Figure 253. BESTlogicPlus Settings (Phase Mode) Step 3: Use BESTCOMSPlus to open the Protection, Current, Instantaneous Ov

Página 283 - Timekeeping

9424200996 Rev L 341 Table 133. Timing Test Settings (Phase Mode) Pickup Setting Time Delay 0.5 A 2,000 ms 0.5 A 5,000 ms 0.5 A 10,000 ms Step 3: Co

Página 284 - Setting the Time and Date

342 9424200996 Rev L Step 3: Use BESTCOMSPlus to open the Protection, Current, Instantaneous Overcurrent (50-1) screen and send the low range te

Página 285 - IRIG Port

9424200996 Rev L 343 Pickup Verification (I2 Mode) Step 1: Use BESTCOMSPlus to send the operational settings in Table 137 to the BE1-11m. Reset al

Página 286

344 9424200996 Rev L for a 1 A BE1-11m with a pickup setting of 0.1, it would require 0.1 times 3 or 0.3 amperes of input current. Step 6: Slowly

Página 287

9424200996 Rev L 345 Table 140. Operational Settings (IG Mode) Setting Value BESTCOMSPlus Screen Description Ground CT Ratio 1 System Parameters, Sen

Página 288

346 9424200996 Rev L Step 8: (Optional.) Repeat steps 1 through 7 for settings group 1, 2, and 3. Step 9: (Optional.) Repeat steps 1 through

Página 289 - Device Information

9424200996 Rev L 347 Timing Verification (Phase Mode) Time Delay Range = 0 to 60,000 ms Timing Accuracy = ±0.5% or ±½ cycle, whichever is greater + 3

Página 290 - Device Info

24 9424200996 Rev L Entering Usernames and Passwords If password security has been initiated for a function, the front-panel display will prompt yo

Página 291

348 9424200996 Rev L Step Pickup Setting Low Actual Pickup High Low* Actual Dropout High* Pass/Fail I2 IA I2 IA I2 IA I2 IA I2 IA 6 0.5 (5A CT) 1.5

Página 292

9424200996 Rev L 349 Timing Verification (IG Mode) Time Delay Range = 0 to 60,000 ms Timing Accuracy = ±0.5% or ±½ cycle, whichever is greater + 3 cy

Página 293 - Configuration

350 9424200996 Rev L Instantaneous Overcurrent (50) Test BE1-11m

Página 294 - Power Measurement

9424200996 Rev L 351 Breaker Fail (50BF) Test Functional testing is a way to assess this protection system’s suitability for your application. Functi

Página 295 - VarsVarsVarsVars ++=

352 9424200996 Rev L • Fault recording is enabled. • Breaker Status is closed with /IN1. Figure 257. BESTlogicPlus Settings (BFI52 Contact Initi

Página 296 - Motor Configuration Settings

9424200996 Rev L 353 Setting Value BESTCOMSPlus Screen Description Pickup 2 A Protection, Current, Instantaneous Overcurrent (50-1) Sets pickup to 2

Página 297 - Settings

354 9424200996 Rev L Setting Value BESTCOMSPlus Screen Description Delay Timer 200 ms Protection, Current, Breaker Fail (50BF) Sets delay timer to

Página 298 - CT Setup

9424200996 Rev L 355 Inverse Overcurrent (51) Test Functional testing is a way to assess this protection system’s suitability for your application. F

Página 299 - Bus CT Selection

356 9424200996 Rev L Figure 259. BESTlogicPlus Settings (Phase Mode) Step 3: Use BESTCOMSPlus to open the Protection, Current, Inverse Overcurr

Página 300 - Display Units

9424200996 Rev L 357 Step 2: Prepare to monitor the 51-1 timings. Timing accuracy is verified by measuring the elapsed time between a sensing curren

Página 301 - Introduction to Testing

9424200996 Rev L 25 Performing Control Operations Control operations can be executed by navigating to Metering, Control. These functions allow you to

Página 302 - Performance Testing

358 9424200996 Rev L Table 150. Operational Settings (3I0 Mode) Setting Value BESTCOMSPlus Screen Description Phase CT Ratio 1 System Parameters, S

Página 303 - Event Reporting Features

9424200996 Rev L 359 Step 8: (Optional.) Repeat steps 1 through 7 for settings group 1, 2, and 3. Step 9: (Optional.) Repeat steps 1 through 8

Página 304

360 9424200996 Rev L Pickup Verification (I2 Mode) Step 1: Use BESTCOMSPlus to send the operational settings in Table 154 to the BE1-11m. Reset

Página 305 - Acceptance Testing

9424200996 Rev L 361 for a 1 A BE1-11m with a pickup setting of 0.1, it would require 0.1 times 3 or 0.3 amperes of input current. Step 6: Slowly in

Página 306 - Control Outputs

362 9424200996 Rev L Step 7: (Optional.) Repeat steps 1 through 6 for 51-2, 51-3, 51-4, and 51-5. Step 8: (Optional.) Repeat steps 1 through 7 wi

Página 307 - Current Circuit Verification

9424200996 Rev L 363 Table 159. Pickup Test Settings (IG Mode) Sensing Input Type Range Pickup Setting Time Dial Time Curve 5 A Low 0.5 A 0 I2 Mid

Página 308

364 9424200996 Rev L Table 161. Timing Test Settings (IG Mode) Sensing Type Time Dial Applied Current 5 A 0.5 1.00 A 2.50 A 12.50 A 5.0 1.00 A 2.50

Página 309 - Power Reading Verification

9424200996 Rev L 365 Dropout should occur between 93-99% of the actual pickup value. Step Pickup Setting Low Actual Pickup High Low* Actual Dropout

Página 310 - Frequency Verification

366 9424200996 Rev L Dropout should occur between 93-99% of the actual pickup value. Step Pickup Setting Low Actual Pickup High Low* Actual Dropo

Página 311 - Commissioning Testing

9424200996 Rev L 367 Dropout should occur between 93-99% of the actual pickup value. Step Pickup Setting Low Actual Pickup High Low* Actual Dropout H

Página 312 - Virtual Control Switch

26 9424200996 Rev L Figure 23. Front-Panel Display Setup Screen Table 3. Settings for Front-Panel Display Setup Locator Setting Range Increment Un

Página 313 - Clock Display

368 9424200996 Rev L Pickup Verification (IG Mode) Pickup Setting Range = 0.5 to 16 A for 5A sensing 0.1 to 3.2 A for 1A sensing 0.01 to 0.8 A

Página 314 - Targets

9424200996 Rev L 369 4 5.0 I2 0.50 A 1.798 sec 1.988 sec P / F 4 5.0 I2 2.50 A 0.944 sec 1.044 sec P / F 4 9.9 I2 0.20 A 8.300 sec 9.173 s

Página 315 - In Service Readings

370 9424200996 Rev L Inverse Overcurrent (51) Test BE1-11m

Página 316

9424200996 Rev L 371 Phase Current Differential (87) Test Functional testing is a way to assess this protection system’s suitability for your applica

Página 317

372 9424200996 Rev L Setting Value BESTCOMSPlus Screen Description 27/59 Mode PN System Parameters, Sensing Transformers Sets 27/59 mode to phase-n

Página 318

9424200996 Rev L 373 Step 5: Slowly increase the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the pickup. This should occur at

Página 319 - Functional Test Procedure

374 9424200996 Rev L Setting Value BESTCOMSPlus Screen Description Phase VT Ratio 1 System Parameters, Sensing Transformers Sets phase VT ratio to

Página 320 - Timing Verification

9424200996 Rev L 375 Step 10: To test the Restraint Slope 1 setting, connect two balanced three-phase current sources to the BE1-11m in ABC rotation

Página 321 - Functional Test Report

376 9424200996 Rev L Step Pickup Setting Low Actual Pickup High Low Actual Dropout High Pass/Fail 15 – Slope 2 8.83 A 8.66 A 9.00 A N/A* N/A* N/

Página 322

9424200996 Rev L 377 Power (32) Test Functional testing is a way to assess this protection system’s suitability for your application. Functional test

Página 323 - Phase Overvoltage (59P) Test

9424200996 Rev L 27 Contact Inputs and Outputs BE1-11m Motor Protection Systems provide seven contact inputs, eight general-purpose contact outputs,

Página 324

378 9424200996 Rev L Setting Value BESTCOMSPlus Screen Description 32-1 A Over Enabled Target Configuration, Targets Enables phase A over target fo

Página 325

9424200996 Rev L 379 Step 8: (Optional.) Repeat steps 1 through 7 with CT2 as the bus CT selection for protection systems equipped with two sets o

Página 326

380 9424200996 Rev L Step 6: (Optional.) Repeat steps 1 through 5 for B-phase and C-phase currents. (Consult the Power (32) Protection chapter f

Página 327

9424200996 Rev L 381 Reverse Tripping Direction (Overpower) Pickup Setting Range = 1 to 6,000 Watts for 5A sensing 1 to 1,200 Watts for 1A sensing

Página 328

382 9424200996 Rev L Power (32) Test BE1-11m

Página 329

9424200996 Rev L 383 Loss of Excitation - Reverse Var Based (40Q) Test Functional testing is a way to assess this protection system’s suitability for

Página 330

384 9424200996 Rev L Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in Figure 265. • Blocking is disabled. •

Página 331

9424200996 Rev L 385 Step 2: Prepare to monitor the 40Q timings. Timing accuracy is verified by measuring the elapsed time between a sensing current

Página 332

386 9424200996 Rev L Loss of Excitation - Reverse Var Based (40Q) Test BE1-11m

Página 333

9424200996 Rev L 387 Power Factor (55) Test Functional testing is a way to assess this protection system’s suitability for your application. Function

Página 334

ii 9424200996 Rev L 12570 State Route 143 Highland IL 62249-1074 USA www.basler.com [email protected] Tel: +1 618.654.2341 Fax: +1 618.654.2351

Página 335

28 9424200996 Rev L input(s) that you want to configure. Observe all electrostatic discharge (ESD) precautions when handling the BE1-11m. 3. Using

Página 336

388 9424200996 Rev L Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 266. • Blocking is disabled. •

Página 337

9424200996 Rev L 389 Step 3: Connect and apply 5A∠0° to terminals D1 (A-phase polarity) and D2 (A-phase non-polarity) and a three-phase 69.28 V phas

Página 338

390 9424200996 Rev L Timing Verification Time Delay Range = 0 ms or 50 to 600,000 ms Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater Ste

Página 339 - Frequency (81) Test

9424200996 Rev L 391 Thermal Curve (49TC) Test Functional testing is a way to assess this protection system’s suitability for your application. Funct

Página 340

392 9424200996 Rev L Setting Value BESTCOMSPlus Screen Description Full Load Amps 2 System Parameters, Motor Configuration Sets Full Load Amps to 3

Página 341 - Time Delay Verification

9424200996 Rev L 393 Where: S = Overload Scaler SF = Scale Factor FLA = Full Load Amps The Equivalent Thermal Current is calculated in Equati

Página 342

394 9424200996 Rev L The Steady State Thermal Capacity (TCU) is calculated in Equation 25. =× 1      

Página 343

9424200996 Rev L 395 starting). Verify that OUT2 (Overloaded) closes indicating an overloaded condition. Verify that the Starting LED is lit on the f

Página 344

396 9424200996 Rev L Setting Value BESTCOMSPlus Screen Description Element Mode Standard Curve Protection, Thermal, Thermal Curve (49TC) Selects St

Página 345

9424200996 Rev L 397 Step 21: Navigate to Metering, Motor, Motor Meter on the front-panel display and verify that Thermal Capacity is 0%. Step 22:

Página 346

9424200996 Rev L 29 At this point, the logic variable will change from an energized (logic 1 or true) state to a de-energized (logic 0 or false) stat

Página 347

398 9424200996 Rev L Setting Value BESTCOMSPlus Screen Description Hot Safe Stall Time 1 Protection, Thermal, Thermal Curve (49TC) Sets Hot Safe St

Página 348

9424200996 Rev L 399 Timing Verification (Standard Curve) Time Dial Range = 1 to 20 Timing Accuracy = ±5% or ±2½ cycles, whichever is greater Step Ti

Página 349

400 9424200996 Rev L Thermal Curve (49TC) Test BE1-11m

Página 350

9424200996 Rev L 401 Incomplete Sequence (48) Test Functional testing is a way to assess this protection system’s suitability for your application. F

Página 351

402 9424200996 Rev L Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in Figure 270. Note that OUT3 (Running) sh

Página 352

9424200996 Rev L 403 Starts per Time Interval (66) Test Functional testing is a way to assess this protection system’s suitability for your applicati

Página 353

404 9424200996 Rev L Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in Figure 271. Figure 271. BESTlogicPlus

Página 354

9424200996 Rev L 405 Step 7: Apply 10 Aac three-phase current for approximately one minute (simulate motor starting). Note that this is the second s

Página 355

406 9424200996 Rev L Starts per Time Interval (66) Test BE1-11m

Página 356

9424200996 Rev L 407 Restart Inhibit Test Functional testing is a way to assess this protection system’s suitability for your application. Functional

Página 357

30 9424200996 Rev L See Table 5 for a list of settings and their defaults. Table 5. Contact Input Settings Setting Range Increment Unit Default Lab

Página 358

408 9424200996 Rev L Figure 273. BESTlogicPlus Settings Step 3: Prepare to monitor restart inhibit function operation. Operation can be verified

Página 359

9424200996 Rev L 409 Step 15: Remove three-phase current. Verify that OUT1 (Starting) opens and OUT2 (Stopped) closes. Step 16: Apply 10 Aac three-

Página 360

410 9424200996 Rev L Restart Inhibit Test BE1-11m

Página 361

9424200996 Rev L 411 Virtual Control Switches (43) Test Functional testing is a way to assess this protection system’s suitability for your applicati

Página 362

412 9424200996 Rev L Figure 274. BESTlogicPlus Settings Figure 275. BESTCOMSPlus Virtual Switches Control Screen Step 5: Click the 43-1 button

Página 363 - Breaker Fail (50BF) Test

9424200996 Rev L 413 Step 3: Use the Metering Explorer of BESTCOMSPlus to open the Control, Virtual Switches tree branch (Figure 275). Using selec

Página 364

414 9424200996 Rev L Virtual Control Switches (43) Test BE1-11m

Página 365

9424200996 Rev L 415 Logic Timers (62) Test Functional testing is a way to assess this protection system’s suitability for your application. Function

Página 366

416 9424200996 Rev L Step 3: Steps 4 through 6 will initiate the 62-1 timer by changing the 43-1 switch state to ON (logic 1). Once initiated, t

Página 367

9424200996 Rev L 417 Figure 278. Pickup/Dropout Mode Step 10: (Optional.) Repeat steps 1 through 9 for 62-1, 62-2, 62-3, 62-4, 62-5, 62-6, 62-7, an

Página 368

9424200996 Rev L 31 1. The relay trouble alarm disables all hardware outputs. 2. The programmable hold timer is active. 3. The select-before-opera

Página 369

418 9424200996 Rev L despite a second 43-1 OFF to ON initiate signal while the duration timer was active. Figure 279 illustrates the timing relatio

Página 370

9424200996 Rev L 419 Note The 43-1 switch action is performed three times in this test. To illustrate the action of the timer mode, step 4 should be

Página 371

420 9424200996 Rev L Step 2: Steps 3 through 5 supply the 62-1 timer with a block input by changing the 43-1 switch state to ON. You can view th

Página 372

9424200996 Rev L 421 Figure 281. Integrating Timer Mode Latched Mode Step 1: Use BESTCOMSPlus to send the operational settings in Table 186 to th

Página 373

422 9424200996 Rev L Figure 282. BESTlogicPlus Settings (Latched Mode) Note The 43-1 switch action is performed twice in this test. The 43-2 swit

Página 374

9424200996 Rev L 423 Figure 283. Latched Mode Functional Test Report Function Pass/Fail Pickup/Dropout Mode P / F One-Shot Non-Retriggerable Mo

Página 375

424 9424200996 Rev L Logic Timers (62) Test BE1-11m

Página 376

9424200996 Rev L 425 Lockout Functions (86) Test Functional testing is a way to assess this protection system’s suitability for your application. Fun

Página 377

426 9424200996 Rev L Step 5: Apply voltage to IN1. Verify that OUT1 closes and remains closed. Step 6: Power down the BE1-11m and verify that

Página 378

9424200996 Rev L 427 Breaker Control Switch (101) Test Functional testing is a way to assess this protection system’s suitability for your applicatio

Página 379

32 9424200996 Rev L Programmable Hold Timer—Hold Attribute Historically, electromechanical relays have provided trip contact seal-in circuits. Thes

Página 380

428 9424200996 Rev L Figure 285. BESTlogicPlus Settings Step 5: Place the 101 in the CLOSE position by using the Metering Explorer in BESTCOMSP

Página 381

9424200996 Rev L 429 Frequently Asked Questions (FAQ) Electrical/Connections Is the power supply polarity sensitive? No, the power supply will accept

Página 382

430 9424200996 Rev L How can I check the version number of my BE1-11m? The application version can be found in four different ways: One, on the Set

Página 383

9424200996 Rev L 431 Troubleshooting Basler microprocessor-based protection systems are similar in nature to a panel of electromechanical or solid-st

Página 384

432 9424200996 Rev L withdrawn and any unsaved changes are lost. When activity at a port is no longer required, access should be terminated. Obtain

Página 385

9424200996 Rev L 433 Why don't the targets or trip LED work properly? If a protective element is tripping at the desired level, but the targets

Página 386

434 9424200996 Rev L Troubleshooting BE1-11m

Página 387 - Functional Test Reports

9424200996 Rev L 435 Specifications BE1-11m protection systems used in 50/60 Hz systems have the following features and capabilities. For 25 Hz opera

Página 388

436 9424200996 Rev L Reactive Power 5 Ampere CT Range ... –7,500 var to +7,500 var 1 Ampere CT Range

Página 389 - Power (32) Test

9424200996 Rev L 437 37 - Instantaneous Undercurrent Protection Pickup 5 Ampere CT Setting Range ... 0.5 to 100 A 1

Página 390

9424200996 Rev L 33 Figure 30. Contact Outputs Screen Contact Output Logic Override Control BESTCOMSPlus Navigation Path: Metering Explorer, Control

Página 391

438 9424200996 Rev L Time Delay Setting Range ... 0 to 600,000 ms Accuracy...

Página 392

9424200996 Rev L 439 50BF - Breaker Failure Protection Phase & Ground Pickup 5 Ampere CT Setting Range ... 0.25

Página 393

440 9424200996 Rev L 59P - Phase Overvoltage Protection Pickup Setting Range ... 1 to 300 V

Página 394

9424200996 Rev L 441 81 - Frequency Protection O/U Pickup Setting Range ... 15 to 70 Hz Accur

Página 395 - (40Q) Test

442 9424200996 Rev L Restraint Slope 1 Setting Range ... 5 to 100% Restraint Slope 2 Settin

Página 396

9424200996 Rev L 443 1 Ampere CT Continuous Rating ... 4 A One Second Rating ...

Página 397

444 9424200996 Rev L Option 2 (125/250 Vac/dc) DC Operating Range ... 90 to 300 Vdc AC Operating Rang

Página 398

9424200996 Rev L 445 Input Burden Burden values shown in Table 191 assume nominal value of input voltage applied. Table 191. Contact-Sensing Input Bu

Página 399 - Power Factor (55) Test

446 9424200996 Rev L Clock Holdup Capacitor Holdup Time ... Up to 24 hours depending on conditions Batter

Página 400

9424200996 Rev L 447 Panel Display 64 by 128 dot pixels LCD with LED backlight. Operating Temperature ... –

Página 401

34 9424200996 Rev L In the Action column, select Pulse from the drop-down menu and click on the green arrow to the right. Pulse override control ca

Página 402

448 9424200996 Rev L • EN 50178 – Electronic Equipment for use in Power Installations • EN 61000-6-2 – Electromagnetic Compatibility (EMC), Gener

Página 403 - Thermal Curve (49TC) Test

9424200996 Rev L 449 IEC 61850 Certification KEMA certified per IEC 61850 Certificate Level A. Physical Weight ...

Página 404

450 9424200996 Rev L Specifications BE1-11m

Página 405

9424200996 Rev L 451 Specifications - 25 Hz Operation BE1-11m protection systems used in 25 Hz systems have the following features and capabilities.

Página 406

452 9424200996 Rev L Reactive Power 5 Ampere CT Range ... –7,500 var to +7,500 var 1 Ampere CT Range

Página 407 - RTD Biasing (Optional)

9424200996 Rev L 453 37 - Instantaneous Undercurrent Protection Pickup 5 Ampere CT Setting Range ... 0.5 to 100 A 1

Página 408 - RTD Module

454 9424200996 Rev L Time Delay Setting Range ... 0 to 600,000 ms Accuracy...

Página 409 - User Curve

9424200996 Rev L 455 50BF - Breaker Failure Protection Phase & Ground Pickup 5 Ampere CT Setting Range ... 0.25

Página 410

456 9424200996 Rev L 59P - Phase Overvoltage Protection Pickup Setting Range ... 1 to 300 V

Página 411

9424200996 Rev L 457 81 - Frequency Protection O/U Pickup Setting Range ... 15 to 70 Hz Accur

Página 412

9424200996 Rev L 35 Phase Undervoltage (27P) Protection Four phase undervoltage (27P) elements monitor the sensing voltage applied to the BE1-11m. An

Página 413

458 9424200996 Rev L Restraint Slope 1 Setting Range ... 5 to 100% Restraint Slope 2 Settin

Página 414

9424200996 Rev L 459 Time Curve Characteristics This chapter provides time curve information for the inverse overcurrent (51), under/overvoltage (27/

Página 415

460 9424200996 Rev L Curve Selection Curve Name Trip Characteristic Constants Reset ∗ A B C N K R A1 IEC Inverse 0.14 0 1 0.02 0 20 I1 CO Inverse T

Página 416 - Figure 272. Test Sequence

9424200996 Rev L 461 Table 193. Characteristic Curve Cross-Reference Curve Curve Name Similar To S1 CO Short Inverse ABB CO-2 S2 IAC Short Inverse GE

Página 417

462 9424200996 Rev L Basler Electric protection systems have a maximum time dial setting of 9.9. The Basler Electric equivalent time dial setting f

Página 418

9424200996 Rev L 463 The K factor gives the time that a generator can withstand 1 per unit negative sequence current. For example, with a K factor of

Página 419 - Restart Inhibit Test

464 9424200996 Rev L Figure 287. Time Characteristic Curve S1, Short Inverse (Similar to ABB CO-2) Time Curve Characteristics BE1-11m

Página 420 - Time Between Starts

9424200996 Rev L 465 Figure 288. Time Characteristic Curve S2, Short Inverse (Similar To GE IAC-55) BE1-11m Time Curve Characteristics

Página 421

466 9424200996 Rev L Figure 289. Time Characteristic Curve A, Standard Inverse (BS 142) Time Curve Characteristics BE1-11m

Página 422

9424200996 Rev L 467 Figure 290. Time Characteristic Curve A1, Inverse (IEC 60255-151 Ed. 1) BE1-11m Time Curve Characteristics

Página 423

36 9424200996 Rev L Trip The Trip output becomes true when an undervoltage pickup condition persists for the duration of the element Time Delay set

Página 424 - Switch Mode

468 9424200996 Rev L Figure 291. Time Characteristic Curve I1, Inverse Time (Similar to ABB CO-8) Time Curve Characteristics BE1-11m

Página 425

9424200996 Rev L 469 Figure 292. Time Characteristic Curve I2, Inverse Time (Similar to GE IAC-51) BE1-11m Time Curve Characteristics

Página 426

470 9424200996 Rev L Figure 293. Time Characteristic Curve M, Moderately Inverse (Similar to ABB CO-7) Time Curve Characteristics BE1-11m

Página 427 - Logic Timers (62) Test

9424200996 Rev L 471 Figure 294. Time Characteristic Curve D1, Moderately Inverse (IEC 60255-151 Ed. 1) 0.010.101.0010.00100.001000.001 10 100MUL

Página 428

472 9424200996 Rev L Figure 295. Time Characteristic Curve L1, Long Inverse (Similar to ABB CO-5) Time Curve Characteristics BE1-11m

Página 429

9424200996 Rev L 473 Figure 296. Time Characteristic Curve L2, Long Inverse (Similar To GE IAC-66) BE1-11m Time Curve Characteristics

Página 430 - 02-27-06

474 9424200996 Rev L Figure 297. Time Characteristic Curve G, Long Time Inverse (BS 142) Time Curve Characteristics BE1-11m

Página 431 - P0035-32

9424200996 Rev L 475 Figure 298. Time Characteristic Curve V1, Very Inverse (Similar to ABB CO-9) BE1-11m Time Curve Characteristics

Página 432

476 9424200996 Rev L Figure 299. Time Characteristic Curve V2, Very Inverse (Similar to GE IAC-53) Time Curve Characteristics BE1-11m

Página 433 - Latched Mode

9424200996 Rev L 477 Figure 300. Time Characteristic Curve B, Very Inverse (BS 142) BE1-11m Time Curve Characteristics

Página 434

9424200996 Rev L 37 Operational Settings Phase undervoltage element operational settings are configured on the Undervoltage (27P) settings screen (Fi

Página 435

478 9424200996 Rev L Figure 301. Time Characteristic Curve B1, Very Inverse (IEC 60255-151 Ed. 1) Time Curve Characteristics BE1-11m

Página 436

9424200996 Rev L 479 Figure 302. Time Characteristic Curve E3, Very Inverse (IEC 60255-151 Ed. 1) 0.010.101.0010.00100.001000.001 10 100MULTIPLES

Página 437 - Lockout Functions (86) Test

480 9424200996 Rev L Figure 303. Time Characteristic Curve E1, Extremely Inverse (Similar to ABB CO-11) Time Curve Characteristics BE1-11m

Página 438

9424200996 Rev L 481 Figure 304. Time Characteristic Curve E2, Extremely Inverse (Similar to GE IAC-77) BE1-11m Time Curve Characteristics

Página 439

482 9424200996 Rev L Figure 305. Time Characteristic Curve C, Extremely Inverse (BS 142) Time Curve Characteristics BE1-11m

Página 440

9424200996 Rev L 483 Figure 306. Time Characteristic Curve C1, Extremely Inverse (IEC 60255-151 Ed. 1) BE1-11m Time Curve Characteristics

Página 441 - General Operation

484 9424200996 Rev L Figure 307. Time Characteristic Curve F1, Extremely Inverse (IEC 60255-151 Ed. 1) 0.010.101.0010.00100.001000.001 10 100MU

Página 442

9424200996 Rev L 485 Figure 308. Time Characteristic Curve D, Definite Time (Similar To ABB CO-6) BE1-11m Time Curve Characteristics

Página 443 - Troubleshooting

486 9424200996 Rev L Figure 309. 46 Time Characteristic Curve NOTE: Curves are shown as extending farther to the left than they will in practice.

Página 444 - Metering/Display

9424200996 Rev L 487 Under/Overvoltage (27/59) The 27 and 59 elements have independent user defined definite and inverse time delays. The inverse tim

Página 445

9424200996 Rev L iii Contents Introduction ...

Página 446

38 9424200996 Rev L Phase Undervoltage (27P) Protection BE1-11m

Página 447 - Specifications

488 9424200996 Rev L Figure 310. Undervoltage (27) Inverse Time Curve 0.101.0010.00100.000 1TIME IN SECONDS MULTIPLES OF PICKUP 9.99876543210.5

Página 448 - 32 - Power Protection

9424200996 Rev L 489 Overvoltage (59) Inverse Time Curve The overvoltage inverse time curve is defined by Equation 34 and shown in Figure 311. =

Página 449 - °C minimum

490 9424200996 Rev L Figure 311. Overvoltage (59) Inverse Time Curve 0.101.0010.00100.001 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2TIME IN SECONDS

Página 450

9424200996 Rev L 491 Thermal Curve (49TC) The Standard and IEC curves are defined below. Standard Curve The Standard Curve Time Dial setting determin

Página 451 - 55 - Power Factor Protection

492 9424200996 Rev L The standard curve is illustrated in Figure 312. Figure 312. 49TC Standard Curve 0.11101001000100000 2 4 6 8 10 12 14TIME

Página 452 - 62 - Logic Timers

9424200996 Rev L 493 IEC Curve IEC curves provide the ability to automatically change between two curves based on if the motor is hot or cold. The ho

Página 453 - 81 - Frequency Protection

494 9424200996 Rev L The IEC Curve is illustrated in Figure 313. Figure 313. 49TC IEC Curve 0.11101001000100001000000 2 4 6 8 10 12 14TIME IN SE

Página 454 - General Specifications

9424200996 Rev L 495 RTD Module The RTD (Resistance Temperature Detector) module is an optional remote device that provides RTD inputs, analog inputs

Página 455 - Power Supply

496 9424200996 Rev L Mounting RTD modules are contained in a potted plastic case and may be mounted in any convenient position. The construction of

Página 456 - Contact-Sensing Inputs

9424200996 Rev L 497 Terminations The terminal interface consists of permanently mounted connectors with screw-down compression terminals. RTD module

Página 457 - Real-Time Clock

9424200996 Rev L 39 Negative-Sequence Voltage (47) Protection Negative-sequence voltage protection is included as a mode of the 59X (Auxiliary Overvo

Página 458

498 9424200996 Rev L Figure 315. Input and Output Terminals Table 197. Input and Output Terminals Connector Description TB1 Operating Power and Al

Página 459 - CE Compliance

9424200996 Rev L 499 Figure 316. Analog Inputs - Voltage Input Connections Figure 317. Analog Inputs - Current Input Connections External RTD Input

Página 460 - Warning! - EXPLOSION HAZARD

500 9424200996 Rev L Figure 319. External Three-Wire RTD Input Connections RTD Module Communications Setup Procedure Communication between the BE1

Página 461 - Physical

9424200996 Rev L 501 5. Open the RTD Module plugin in BESTCOMSPlus. 6. Pull down the Communication menu and select New Connection  RTD Module. The

Página 462

502 9424200996 Rev L Figure 321. Procedure 2 Connect to RTD Module 1. Connect an Ethernet cable directly between the PC and RTD module. 2. Apply

Página 463 - Operational Specifications

9424200996 Rev L 503 10. Click Send to Device. A password is required. The default password is “OEM”. Click Close. 11. Click Cancel on the Device Dis

Página 464

504 9424200996 Rev L Figure 322. BESTCOMSPlus Select Language Screen The BESTCOMSPlus splash screen is shown for a brief time. See Figure 323. Fi

Página 465

9424200996 Rev L 505 Figure 325. RTD Module Connection Screen Wait until scanning is complete. See Figure 326. Figure 326. Scanning for Connected D

Página 466

506 9424200996 Rev L The Configure - RTD Module screen shown in Figure 328 appears. The BE1-11m uses the Device Address to communicate with the con

Página 467

9424200996 Rev L 507 screen is found by selecting Activate Device from the Tools pull-down menu of the BESTCOMSPlus main screen. Device Info Informat

Página 468

40 9424200996 Rev L Negative-Sequence Voltage (47) Protection BE1-11m

Página 469

508 9424200996 Rev L Figure 332. Login Screen Enter the Password and then click the Log In button. The default password is “OEM”. The Device Secur

Página 470

9424200996 Rev L 509 Figure 334. Module 1 Input #1 Screen Table 198 summarizes the configuration settings for remote analog inputs. Table 198. Confi

Página 471 - Time Curve Characteristics

510 9424200996 Rev L Figure 335. Module 1 Output #1 Screen Table 199 summarizes the configuration settings for remote analog outputs. Table 199. C

Página 472

9424200996 Rev L 511 Figure 336. RTD Type Selection Screen The source for the 49RTD protection elements can be set for RTD Group 1, 2, 3, 4, 5, 6, o

Página 473

512 9424200996 Rev L Analog Outputs The RTD module contains four programmable analog outputs. Rating ... 4 to

Página 474 - Equation 28

9424200996 Rev L 513 IEC 60255-21-1: Vibration, Shock, Bump, and Seismic Tests on Measuring Relays and Protective Equipment (Section 1 - Vibration T

Página 475 - Equation 32

514 9424200996 Rev L Physical Weight ... 2.15 lb (0.975 kg) IP Class ... IP

Página 476 - 464 9424200996 Rev L

9424200996 Rev L 515 Settings Calculation Examples This chapter provides settings calculation examples for setting the BE1-11m for an induction motor

Página 477 - 9424200996 Rev L 465

516 9424200996 Rev L Motor Manufacturer Data Motor manufacturer data should be reviewed before configuring the BE1-11m. Typical motor manufacturer

Página 478 - 466 9424200996 Rev L

9424200996 Rev L 517 The required motor curves are shown in Figure 339. Curve A shows the thermal limits at 100% of the starting voltage. Curve B sho

Página 479 - 9424200996 Rev L 467

9424200996 Rev L 41 Phase Overvoltage (59P) Protection Two phase overvoltage (59P) elements monitor the sensing voltage applied to the BE1-11m. An el

Página 480 - 468 9424200996 Rev L

518 9424200996 Rev L General Settings Display Units Settings in this example are in metric and secondary units, based upon multiples of FLA (Full L

Página 481 - 9424200996 Rev L 469

9424200996 Rev L 519 System Parameters - Sensing Transformers Phase CT Ratios The motor manufacturer data for full-load amps (FLA) is 363 A under nor

Página 482 - 470 9424200996 Rev L

520 9424200996 Rev L System Parameters - Motor Configuration Nominal Settings The system nominal quantities are used for BE1-11m functions such as

Página 483 - MULTIPLES OF PICKUP

9424200996 Rev L 521 Programmable Inputs - Remote RTD RTD Type Selection This settings example uses nine RTDs that are all 100 Ω, platinum. Open the

Página 484 - 472 9424200996 Rev L

522 9424200996 Rev L Figure 346. Programmable Inputs, Remote RTD, RTD Block Configuration Screen Protection - Thermal Thermal Curve (49TC) The 49

Página 485 - 9424200996 Rev L 473

9424200996 Rev L 523 where, Ieq = equivalent thermal current in PU (unit of thermal pickup current) I = maximum phase current in PU I1 = positive-s

Página 486 - 474 9424200996 Rev L

524 9424200996 Rev L Figure 348. Standard Curves RTD Bias Curve The RTD bias curve includes a minimum of three points and a maximum of 40 points.

Página 487 - 9424200996 Rev L 475

9424200996 Rev L 525 Figure 349. Protection, Thermal, RTD Bias Curve Screen Set the Center RTD Bias Temperature (point 2) to the motor hot running t

Página 488 - 476 9424200996 Rev L

526 9424200996 Rev L Figure 350. Protection, Thermal, Resistance Temperature Detector (49RTD-1) Screen Set the 49RTD-2 protection element as shown

Página 489 - 9424200996 Rev L 477

9424200996 Rev L 527 Figure 352. Protection, Current, Instantaneous Overcurrent (50-1) Screen Instantaneous Overcurrent (50-2) - Ground Fault Protec

Página 490 - 478 9424200996 Rev L

42 9424200996 Rev L action. If a target is enabled for the element, the BE1-11m will record a target when the Trip output becomes true. See the Fau

Página 491 - TIME IN SECONDS

528 9424200996 Rev L Figure 354. Protection, Current, Instantaneous Overcurrent (50-3) Screen Instantaneous Overcurrent (50-4) - Overload Protecti

Página 492 - 480 9424200996 Rev L

9424200996 Rev L 529 approaching locked-rotor current, and a reduction in terminal voltage depending upon the motor impedance. The motor can be remov

Página 493 - 9424200996 Rev L 481

530 9424200996 Rev L Figure 357. Motor Differential Connection Example CT Circuit 1 Tap and CT Circuit 2 Tap are shown here, but calculated from t

Página 494 - 482 9424200996 Rev L

9424200996 Rev L 531 Figure 358. 2nd Slope Restrained Operation Example Alarm The BE1-11m provides a Slope % alarm for cases where high loads or thr

Página 495 - 9424200996 Rev L 483

532 9424200996 Rev L Instantaneous Undercurrent (37) - Loss of Load Protection The 37 element protects the motor from overheating by tripping when

Página 496

9424200996 Rev L 533 Figure 361. Protection, Voltage, Undervoltage (27P-1) Screen Undervoltage (27P-2) The 27P-2 protection element is set to trip w

Página 497 - 9424200996 Rev L 485

534 9424200996 Rev L Figure 362. Protection, Voltage, Undervoltage (27P-2) Screen Protection - Frequency Two frequency protection elements monitor

Página 498

9424200996 Rev L 535 Figure 363. Protection, Frequency Screen Overfrequency (81-2) The 81-2 protection element alarms when the source frequency is 5

Página 499 - Under/Overvoltage (27/59)

536 9424200996 Rev L Figure 364. Protection, Incomplete Sequence (48) Screen Protection - Starts per Time Interval (66) The 66 protection element

Página 500

9424200996 Rev L 537 Figure 366. Protection, Restart Inhibit Screen Synchronous Motor Settings Calculation Example This logic and settings scheme is

Página 501

9424200996 Rev L 43 Figure 35. Overvoltage Settings Screen Table 10. Operational Settings Setting Range Increment Unit of Measure Default Mode Disab

Página 502

538 9424200996 Rev L Figure 367. Single-Line Drawing, Phase Differential Protection (5,000 HP Synchronous Motor Example) Motor Manufacturer Data M

Página 503 - Thermal Curve (49TC)

9424200996 Rev L 539 ● FIELD ○ Excitation (Brushless) ...22 kW @ 51 Vdc ○ No Load Saturation P.U. Line Volt

Página 504

540 9424200996 Rev L ● OPERATING PERFORMANCE ○ Load % ... 100 ... 75 ... 50 ○ Ef

Página 505 - Equation 37. Cold Curve

9424200996 Rev L 541 Figure 369. Synchronous Motor V Curves General Settings Display Units Settings in this example are in metric and in secondary u

Página 506

542 9424200996 Rev L Figure 370. General Settings, Display Units Screen Style Number The BE1-11m style number shown in Figure 371 is used in this

Página 507

9424200996 Rev L 543 motor FLA. Enter 60 for the CT ratios on the System Parameters, Sensing Transformers screen shown in Figure 372. Use Wye CT conn

Página 508 - Connections

544 9424200996 Rev L Motor Setup The motor FLA and Service Factor must be entered on the System Parameters, Motor Configuration screen shown in Fig

Página 509 - Alarm Contacts

9424200996 Rev L 545 Figure 375. Programmable Inputs, Remote RTD, RTD Type Selection Screen RTD Block Configuration For this example, the RTDs are c

Página 510

546 9424200996 Rev L Protection - Thermal Thermal Curve (49TC) The 49TC element is the heart of the BE1-11m Motor Protection System. This equivalen

Página 511

9424200996 Rev L 547 overload (upper portion of the curve). Curve 4 is chosen in this example. Set the Standard Curve Time Dial to 4. Figure 378. St

Página 512

44 9424200996 Rev L Phase Overvoltage (59P) Protection BE1-11m

Página 513 - Procedure 2

548 9424200996 Rev L • Running Cool Time Constant - This setting defines the cooling rate of the motor when the 49TC element is not picked up and

Página 514 - = Optional

9424200996 Rev L 549    =   10% +   =(80°1.10)+ 40° = 88°+ 40°= 128°

Página 515

550 9424200996 Rev L Set the 49RTD-1 protection element as shown in Figure 381 to protect the stator winding insulation. Voting is set to 2, meanin

Página 516

9424200996 Rev L 551 = 1.7  (125%  + 2%  )   1 = 1.7 (1.25 + 0.02)755 160= 27.17  

Página 517

552 9424200996 Rev L Instantaneous Overcurrent (50-3) - Unbalance Protection Trip The NEMA MG-1 standard states that the existence of unbalanced vo

Página 518

9424200996 Rev L 553 =120  (5%)  (4) =125% 4 = 10% Equation 68. 50-4 Pickup Select Unbalance alarm mode, s

Página 519

554 9424200996 Rev L Figure 388. Alarm Settings Screen 50-5 - Overload Protection The 50-5 element is used for overload protection while the motor

Página 520 - Configuration Settings

9424200996 Rev L 555 The motor can be removed from service faster when using the 50-6 element instead of the 49TC element for jam protection. This fa

Página 521

556 9424200996 Rev L Figure 391. Motor Differential Connection Example This example uses percent differential mode. The motor must have all six st

Página 522 - Remote RTDs Configuration

9424200996 Rev L 557 Equation 73. 2nd Slope (Starting) Pickup Setting Figure 392 shows an example of 2nd Slope Restrained Operation. Figure 392. 2nd

Página 523

9424200996 Rev L 45 Auxiliary Overvoltage (59X) Protection Two auxiliary overvoltage (59X) elements monitor the phase and auxiliary voltage applied t

Página 524 - Communication Interface

558 9424200996 Rev L Figure 393. Protection, Current, Current Differential (87) Screen User Programmable Alarm User Programmable Alarm 3 is used f

Página 525 - CSA Certification

9424200996 Rev L 559 Figure 394. Protection, Current, Instantaneous Undercurrent (37) Screen Protection - Voltage Two undervoltage protection elemen

Página 526 - Storage

560 9424200996 Rev L Figure 395. Protection, Voltage, Undervoltage (27P-1) Screen Undervoltage (27P-2) Starting The 27P-2 protection element is se

Página 527 - 4-kV Bus

9424200996 Rev L 561 Figure 396. Protection, Voltage, Undervoltage (27P-2) Screen Overvoltage (59P-1) The 59-1 protection element is set to trip whe

Página 528 - Motor Manufacturer Data

562 9424200996 Rev L Figure 397. Protection, Voltage, Overvoltage (59P-1) Screen Protection - Power A synchronous motor is started by a prime move

Página 529 - Figure 339. Motor Curves

9424200996 Rev L 563 Figure 398. Logic Pickup / Dropout Timers Screen Figure 399. Power Factor (55) Screen Protection - Frequency Two frequency pro

Página 530 - General Settings

564 9424200996 Rev L Figure 400. Protection, Frequency Screen Overfrequency (81-2) The 81-2 protection element alarms when the source frequency is

Página 531 - Equation 39. Phase VT Ratio

9424200996 Rev L 565 Figure 401. Protection, Incomplete Sequence (48) Screen Protection - Starts per Time Interval (66) The 66 protection element (j

Página 532

566 9424200996 Rev L Figure 403. Protection, Restart Inhibit Screen Logic Programming BESTlogicPlus programmable logic settings for the Synchronou

Página 533

9424200996 Rev L 567 Figure 404. Logic Page 1 (Unchanged from Induction Motor Default) BE1-11m Settings Calculation Examples

Página 534 - Protection - Thermal

46 9424200996 Rev L pickup setting as Vpp in BESTCOMSPlus. See Table 11 for a full list of possible settings. The Aux VT Connection parameter is fo

Página 535

568 9424200996 Rev L Figure 405. Logic Page 2 (Unbalance Trip and Alarm Added) Settings Calculation Examples BE1-11m

Página 536

9424200996 Rev L 569 Figure 406. Logic Page 3 (Power Factor (55) Added) BE1-11m Settings Calculation Examples

Página 537 -   

570 9424200996 Rev L Figure 407. Logic Page 4, Part 1 Settings Calculation Examples BE1-11m

Página 538 - Protection - Current

9424200996 Rev L 571 Figure 408. Logic Page 4, Part 2 Physical outputs remain unchanged. BE1-11m Settings Calculation Examples

Página 539 - Equation 45. 50-3 Pickup

572 9424200996 Rev L Settings Calculation Examples BE1-11m

Página 540 - Equation 47. 50-4 Time Delay

9424200996 Rev L 573 Digital Points The status of all BE1-11m digital points is displayed in the Metering Explorer of BESTCOMSPlus® under Status, Dig

Página 541 - Equation 48. 50-5 Pickup

574 9424200996 Rev L Name Number 43-4 Tag Information 559 43-4 Untag Block 560 43-4 Untag Information 561 43-5 567 43-5 Blocking Tag Status 573 43-

Página 542 - Equation 50. 2

9424200996 Rev L 575 Name Number 49RTD-12 RTD 2-9 1961 49RTD-12 Trip 1940 49RTD-13 Block 1965 49RTD-13 Pickup 1966 49RTD-13 RTD 1-1 1968 49RTD-13 RTD

Página 543 - Equation 52. Slope % Alarm

576 9424200996 Rev L Name Number 49RTD-4 RTD 1-8 1113 49RTD-4 RTD 1-9 1114 49RTD-4 RTD 2-1 1118 49RTD-4 RTD 2-10 1127 49RTD-4 RTD 2-11 1128 49RTD-4

Página 544 - Protection - Voltage

9424200996 Rev L 577 Name Number 49RTD-8 Trip 1832 49RTD-9 Block 1857 49RTD-9 Pickup 1858 49RTD-9 RTD 1-1 1860 49RTD-9 RTD 1-10 1869 49RTD-9 RTD 1-11

Página 545 - Equation 55. 27P-2 Pickup

9424200996 Rev L 47 element Block input to the desired logic in BESTlogicPlus. When the element is initially selected from the Elements view, the def

Página 546 - Protection - Frequency

578 9424200996 Rev L Name Number 51-1 Pos SEQ 301 51-1 Prevent Config Option Change 305 51-1 Residual 293 51-1 Trip 288 51-1 Unbalance 303 51-2 A 3

Página 547 - Equation 57. 81-2 Pickup

9424200996 Rev L 579 Name Number 62-2 Block 599 62-2 Initiate 600 62-3 604 62-3 Block 602 62-3 Initiate 603 62-4 607 62-4 Block 605 62-4 Initiate 606

Página 548 - Protection - Restart Inhibit

580 9424200996 Rev L Name Number Email Email Trigger 6 662 Email Email Trigger 7 663 Email Email Trigger 8 664 Eth Link Lost 734 Ethernet Excess Tr

Página 549

9424200996 Rev L 581 Name Number GGIO-CTL1 Oper16 1612 GGIO-CTL1 Oper16Alarm 1614 GGIO-CTL1 Oper16Default 1613 GGIO-CTL2 Oper01 1615 GGIO-CTL2 Oper01

Página 550

582 9424200996 Rev L Name Number GGIO-CTL4 Oper08Default 1733 GGIO-CTL4 Oper09 1735 GGIO-CTL4 Oper09Alarm 1737 GGIO-CTL4 Oper09Default 1736 GGIO-CT

Página 551 - (exciter)

9424200996 Rev L 583 Name Number Local Contacts Output 4 Override Enable 679 Local Contacts Output 4 Override State 685 Local Contacts Output 4 Remot

Página 552

584 9424200996 Rev L Name Number Setting Change 741 Settings Group 0 811 Settings Group 1 812 Settings Group 2 813 Settings Group 3 814 Settings Gr

Página 553

9424200996 Rev L 585 Revision History Table 202 provides a historical summary of the changes made to the BE1-11m hardware. Application firmware chang

Página 554

586 9424200996 Rev L Firmware Version and Date Change 2.05.00, Oct-11 • Added Output Override Alarms • Added 1A setting range for Full Load Amps

Página 555 - Equation 59. Phase VT Ratio

9424200996 Rev L 587 Firmware Version and Date Change 2.08.02, Aug-14 • Added missing characters to scrolled metering screen • Corrected shifted HM

Página 556

iv 9424200996 Rev L Breaker Failure (50BF) Protection ...

Página 557

48 9424200996 Rev L Table 13. Operational Settings Setting Range Increment Unit of Measure Default Mode* Disabled, 3V0, V1, V2, Vx Fundamental, Vx

Página 558

588 9424200996 Rev L Software Version and Date Change 3.05.03, Feb-14 • Maintenance release 3.06.00, Apr-14 • Added support for BE1-11m firmware

Página 559

9424200996 Rev L 589 Manual Revision and Date Change G, Dec-13 • Added support for BE1-11m firmware version 2.07.00 and BESTCOMSPlus version 3.05.02

Página 560

590 9424200996 Rev L Revision History BE1-11m

Página 562

12570 State Route 143 Highland IL 62249-1074 USA Tel: +1 618.654.2341 Fax: +1 618.654.2351 email: [email protected] P.A.E. Les Pins 67319 Wasselonne

Página 563 - Equation 64. 50-2 Pickup

9424200996 Rev L 49 Frequency (81) Protection Four frequency (81) elements monitor the frequency of the sensing voltage applied to the BE1-11m. An el

Página 564 - Equation 67. 50-3 Pickup

50 9424200996 Rev L Assertion of the Pickup output initiates a timer that begins timing to a trip. The duration of the timer is established by the

Página 565 - Equation 68. 50-4 Pickup

9424200996 Rev L 51 • Faults exceeding the pickup setting by 0.57 Hz/s are detected in 2 cycles • Faults exceeding the pickup setting by 0.24 Hz/s

Página 566 - Equation 70. 50-5 Time Delay

52 9424200996 Rev L Table 14. Logic Inputs and Outputs Name Logic Function Purpose Block Input Disables the 81 function when true Trip Output True

Página 567 - Equation 71. 50-6 Pickup

9424200996 Rev L 53 Instantaneous Undercurrent (37) Protection The instantaneous undercurrent (37) element monitors the three-phase sensing current a

Página 568

54 9424200996 Rev L Inhibit Level The Inhibit Level setting prevents undesired undercurrent tripping on de-energized circuits and during motor star

Página 569

9424200996 Rev L 55 Table 17. Operational Settings Setting Range Increment Unit of Measure Default Mode Disabled or 3 Phase n/a n/a Disabled Source*

Página 570 - Equation 76. 37 Pickup

56 9424200996 Rev L Instantaneous Undercurrent (37) Protection BE1-11m

Página 571

9424200996 Rev L 57 Negative-Sequence Overcurrent (46) Protection Negative-sequence overcurrent protection is included as a mode of the 50 (Instantan

Página 572 - Equation 79. 27P-2 Pickup

9424200996 Rev L v Logic Timers (62) ...

Página 573 - Equation 81. 59P-1 Pickup

58 9424200996 Rev L Figure 43. Sequence Components for an A-B Fault Coordination Settings The 51-x negative-sequence settings should be checked fo

Página 574 - Protection - Power

9424200996 Rev L 59 Instantaneous Overcurrent (50) Protection Six instantaneous overcurrent (50) elements monitor the current applied to the BE1-11m.

Página 575

60 9424200996 Rev L be specified on the System Parameters, Sensing Transformers screen in BESTCOMSPlus. Refer to the Configuration chapter for more

Página 576 - Equation 83. 81-2 Pickup

9424200996 Rev L 61 Table 19. Logic Inputs and Outputs Name Logic Function Purpose Block Input Disables the 50 function when true Trip Output True wh

Página 577

62 9424200996 Rev L Instantaneous Overcurrent (50) Protection BE1-11m

Página 578 - Logic Programming

9424200996 Rev L 63 Breaker Failure (50BF) Protection The breaker failure (50BF) element provides protection and security for the power system agains

Página 579 - 9424200996 Rev L 567

64 9424200996 Rev L Trip The Trip output becomes true if sensed current exceeds the Phase or Ground Pickup setting and the delay time expires in th

Página 580 - 568 9424200996 Rev L

9424200996 Rev L 65 Table 21. Logic Inputs and Outputs Name Logic Function Purpose Block Input Disables the 50BF function when true 50BFI Input Start

Página 581 - 9424200996 Rev L 569

66 9424200996 Rev L Breaker Failure (50BF) Protection BE1-11m

Página 582 - 570 9424200996 Rev L

9424200996 Rev L 67 Inverse Overcurrent (51) Protection Five inverse overcurrent (51) elements monitor the current applied to the BE1-11m. An element

Página 583 - 9424200996 Rev L 571

vi 9424200996 Rev L Power Quality ...

Página 584

68 9424200996 Rev L CT Source The CT Source setting configures an inverse overcurrent element to monitor CT circuit 1 or CT circuit 2 on protection

Página 585 - Digital Points

9424200996 Rev L 69 Curve coefficients are entered on the Inverse Overcurrent (51) settings screen in BESTCOMSPlus. Programmable curve coefficients c

Página 586 - Digital Points BE1-11m

70 9424200996 Rev L elements to annunciate the condition, control other elements in logic, and start the fault recorder (logic element FAULTTRIG).

Página 587 - BE1-11m Digital Points

9424200996 Rev L 71 Figure 49. 51 Phase Pickup Level Compensation   =    × 51  

Página 588 - 576 9424200996 Rev L

72 9424200996 Rev L Element Blocking Fuse Loss The fuse loss element (60FL) can also be set to supervise the 51/27R function. It is possible to set

Página 589 - 9424200996 Rev L 577

9424200996 Rev L 73 Figure 51. Inverse Overcurrent Settings Screen Table 26. Operational Settings Setting Range Increment Unit of Measure Default

Página 590 - 578 9424200996 Rev L

74 9424200996 Rev L Setting Range Increment Unit of Measure Default K Coefficient n/a n/a K Coefficient 0.02800 R Coefficient 0 to 30 0.00001 R C

Página 591 - 9424200996 Rev L 579

9424200996 Rev L 75 Phase Current Differential (87) Protection The phase-current differential (87) element monitors the differential current and prov

Página 592 - 580 9424200996 Rev L

76 9424200996 Rev L element, the BE1-11m will record a target when the Trip output becomes true. See the Fault Reporting chapter for more informati

Página 593 - 9424200996 Rev L 581

9424200996 Rev L 77 Figure 53. Phase Current Differential Settings Screen Figure 54. Phase Current Differential Operation Chart Table 28. Operation

Página 594 - 582 9424200996 Rev L

9424200996 Rev L vii Access Control ...

Página 595 - 9424200996 Rev L 583

78 9424200996 Rev L Setting Range Increment Unit of Measure Default CT Circuit 1 Tap n/a n/a n/a 2 CT Circuit 2 Tap n/a n/a n/a 2 2nd Slope Picku

Página 596 - 584 9424200996 Rev L

9424200996 Rev L 79 Power (32) Protection The power (32) element monitors three-phase real power (watts). The element can be configured to protect ag

Página 597 - Revision History

80 9424200996 Rev L Direction of Power Flow In addition to exceeding the power pickup threshold, direction of power flow (forward or reverse) must

Página 598

9424200996 Rev L 81 Assuming polarity current and voltage connections as shown in Figure 55, forward power is defined as flowing into the Area EPS an

Página 599

82 9424200996 Rev L Logic Connections Power element logic connections are made on the BESTlogicPlus screen in BESTCOMSPlus. The power element logic

Página 600

9424200996 Rev L 83 Loss of Excitation - Reverse Var Based (40Q) Protection The loss of excitation - reverse var based (40Q) element monitors total r

Página 601

84 9424200996 Rev L Assertion of the Pickup output initiates a timer that begins timing to a trip. The duration of the timer is established by the

Página 602

9424200996 Rev L 85 Figure 61. Loss of Excitation - Reverse var Based Settings Screen Table 32. Operational Settings Setting Range Increment Unit of

Página 603

86 9424200996 Rev L Loss of Excitation - Reverse Var Based (40Q) Protection BE1-11m

Página 604

9424200996 Rev L 87 Power Factor (55) Protection The power factor (55) element provides synchronous motor pull-out or loss of synchronism protection.

Comentários a estes Manuais

Sem comentários