9289900992 Rev F BE1-851 Modbus Protocol 3-11
Read only:
0 - 300 baud (Do not select for Port 2 Modbus communications.)
1 - 600 baud (Do not select for Port 2 Modbus communications.)
2 - 1200 baud (Do not select for Port 2 Modbus communications.)
3 - 2400 baud
4 - 4800 baud
5 - 9600 baud
6 - 19K baud
40972 Serial Port 1 Relay Address INT
40981 Serial Port 2 Relay Address INT
Read and Write:
0 to 65,534
40964 Serial Port 0 Software Flow Control SI
40973 Serial Port 1 Software Flow Control SI
Read only:
0 if XON / XOFF Control is disabled
1 if XON / XOFF Control is enabled
40965 Serial Port 0 Page Length SI
40974 Serial Port 1 Page Length SI
Read only:
0 for disabled
1 to 40 for number of lines / page
40966 Serial Port 0 Acknowledgement Format SI
40975 Serial Port 1 Acknowledgement Format SI
Read:
0 if No acknowledge
1 if Acknowledge enabled
Write:
0 for No acknowledge
1 to 255 to enable acknowledge
40986 Serial Port 2 Modbus Parity SI
Read and Write:
0 for No parity
1 for Even parity
2 for Odd parity
40987 Serial Port 2 Modbus Remote Delay SI
Read and Write:
1 to 20: 10 to 200 milliseconds
40988 Serial Port 2 Modbus Stop Bits SI
Read and Write:
1 for One stop bit
2 for Two stop bits
40989 Serial Port 2 Modbus Password Security SI
Read and Write:
0 for Disable Password
1 for Enable Password †
When Password Security is disabled, no access is required (Access Password, Access Request, and
Exit holding registers has no effect) and no password protection is used. Global Parameters, holding
registers 40080 to 40099 (ASCII command GF-PW), have no effect on the Modbus serial port, COM 2.