542 9424200994 Rev N
Step 5: Apply voltage to IN1. Verify that OUT1 closes and remains closed.
Step 6: Power down the BE1-11g and verify that OUT1 opens. Wait 10 seconds and power up the
BE1-11g. Verify that OUT1 closes. This verifies that the 86-1 position is stored in non-volatile
memory. Remove voltage from IN1.
Step 7: Connect power supply to IN2 terminals.
Step 8: Apply voltage to IN2. Verify that OUT1 opens and remains open.
Step 9: Apply voltage to both IN1 and IN2. OUT1 should close. This verifies that the Set input has
priority over the Reset input.
Step 10: Repeat steps 1 through 9 for the 86-2 element.
Step 11: Repeat steps 1 through 10 for settings group 1, 2, and 3.
Functional Test Report
Pass/Fail
P / F
Lockout Functions (86) Test BE1-11g