Operational Settings
Phase undervoltage element operational settings are configured on the Undervoltage (27P) settings
screen (Figure 45) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table 15.
Figure 45. Phase Undervoltage Settings Screen
Table 15. Operational Settings
Setting
Range
Increment
Unit of Measure
Default
Mode
Disabled,
One of Three,
Two of Three,
or Three of Three
n/a n/a Disabled
Pickup
0 or 1 to 300
0.1
volts
0
Inhibit Level
0 or 1 to 300
0.1
volts
0
Timing Mode
Definite or Inverse
n/a
n/a
Definite
Time Delay (Definite Timing)
50 to 600,000
varies
milliseconds
50
Time Dial (Inverse Timing)
0 to 9.9
0.1
units
0
BE1-11g Phase Undervoltage (27P) Protection